10
|
Maintenance and service
Installer and user reference guide
34
NOTICE
The R32 refrigerant leakage sensor is a semiconductor detector which may
incorrectly detect substances other than R32 refrigerant. Avoid using chemical
substances (e.g. organic solvents, hair spray, paint) in high concentrations, in the
close proximity of the indoor unit because this may cause misdetection of the R32
refrigerant leakage sensor.
INFORMATION
Lifetime of the sensor is 10 years. The user interface displays error "CH-05" 6 months
before the end of the sensor lifetime and error "CH-02" after the end of the sensor
lifetime. For more information refer to the reference guide of the user interface and
contact you dealer.
In case of detection when the unit is standby
When the detection occurs when the unit is standby, "false detection check" will
occur.
False detection check
1 Unit starts fan operation on the lowest setting.
2 User interface displays error code "A0-13", emits alarm sound and status
indicator is blinking.
3 Sensor checks if refrigerant leakage or misdetection occurred.
If refrigerant leakage is NOT detected, Result:
operation after approximately 2 minutes.
If refrigerant leakage is detected, Result:
1 User interface displays error "A0-11", emits alarm sound and status indicator
is blinking.
2 Contact your dealer immediately. For more information, see the installation
manual of the outdoor unit.
In case of detection when the unit is turned on
1 User interface displays error "A0-11", emits alarm sound and status indicator
is blinking.
2 Contact your dealer immediately. For more information, see the installation
manual of the outdoor unit.
INFORMATION
To stop alarm of the user interface see the reference guide of the user interface.
INFORMATION
The minimum airflow during normal operation or during the refrigerant leakage
detection is always >240 m
system returns to normal
3
/h.
FXDA10~63A2VEB
VRV system air conditioner
4P599621-1A – 2020.10