Specific installer safety instructions

3.1 Instructions for equipment using R32 refrigerant

Installer and user reference guide
14
"21 Configuration" [
Configuration (see
WARNING
In case of R32 refrigerant, terminal connections T1/T2 are for fire alarm input ONLY.
Fire alarm has a higher priority than R32 safety and shuts the entire system down.
X1M
T1
a
T2
a Fire alarm input signal (potential free contact)
WARNING: MILDLY FLAMMABLE MATERIAL
The refrigerant inside this unit is mildly flammable.
WARNING
Do NOT pierce or burn refrigerant cycle parts.
Do NOT use cleaning materials or means to accelerate the defrosting process
other than those recommended by the manufacturer.
Be aware that the refrigerant inside the system is odourless.
WARNING
The appliance shall be stored so as to prevent mechanical damage and in a well-
ventilated room without continuously operating ignition sources (example: open
flames, an operating gas appliance or an operating electric heater) and have a room
size as specified below.
WARNING
Make sure installation, servicing, maintenance and repair comply with instructions
from Daikin and with applicable legislation and are executed ONLY by authorised
persons.
WARNING
If one or more rooms are connected to the unit using a duct system, make sure:
there are no operating ignition sources (example: open flames, an operating gas
appliance or an operating electric heater) in case the floor area is less than the
minimum floor area A (m²).
no auxiliary devices, which may be a potential ignition source, are installed in the
duct work (example: hot surfaces with a temperature exceeding 700°C and
electric switching device);
only auxiliary devices approved by the manufacturer are used in the duct work;
air inlet AND outlet are connected directly to the same room by ducting. Do NOT
use spaces such as a false ceiling as a duct for the air inlet or outlet.