Fault finding
(Fortsetzung)
Display
Verhalten der An-
fault code
lage
F4
Burner in fault state
F5
Burner blocked
F8
Burner in fault state
F9
Burner in fault state
FA
Burner in fault state
Fd
Burner blocked
FE
Burner blocked
Störungsursa-
Maßnahme
che
No flame signal is
Check the ionisation
present.
electrode and leads,
measure the ionisation
current, check the gas
pressure, check the gas
combination valve, igni-
tion, ignition module and
condensate drain.
Press Reset .
Air pressure
Check the air pressure
switch faulty
switch and the intercon-
necting cable.
Fuel valve closes
Check gas combination
too late
valve. Check both con-
trol paths.
Press Reset .
Fan speed too
Check the fan, check
low at burner start
the fan cables and sup-
ply, check the fan con-
trol.
Press Reset .
Fan not at stand-
Check the fan, check
still
the fan cables, check
the fan control.
Press Reset .
Burner control
Check the ignition elect-
unit fault
rodes and leads. Check
whether a strong interfe-
rence (EMC) field exists
near the equipment.
Press Reset .
If the fault is not remo-
ved, replace the control
unit.
Faulty main PCB
Switch OFF the control
unit, if the equipment
will not restart.