Störungsbehebung
Fault finding
(Fortsetzung)
Display
Verhalten der An-
fault code
lage
0b
Burner blocked
30
Burner blocked
38
Burner blocked
60
Control mode
68
Control mode
b1
Control mode
b5
Control mode
E4
Burner blocked
E5
Burner blocked
F0
Burner blocked
F2
Burner in fault state
F3
Burner in fault state
64
Störungsursa-
Maßnahme
che
Flow of Water to
Check the circulation
low.
pump.
Air in heat exc-
Vent the heating sys-
hanger.
tem.
Flow switch faul-
Check the interconnec-
ty.
ting cable.
Boiler temperatu-
Check the boiler tempe-
re sensor shorted
rature sensor (see
out
page 67).
Boiler temperatu-
Check the boiler tempe-
re sensor lead
rature sensor (see
break
page 67).
Return tempera-
Check the return tempe-
ture sensor short-
rature sensor (see
ed out
page 67).
Return tempera-
Check the return tempe-
ture sensor lead
rature sensor (see
break
page 67).
Communication
Check connections and
fault
programm-
replace the programm-
ing unit (internal)
ing unit, if necessary.
Internal fault
Replace control unit.
Fault
supply
Replace control unit.
voltage
Internal fault
Check the ionisation
electrode and leads.
Press Reset .
Internal fault
Replace control unit.
Temperature limi-
Check the heating sys-
ter has respon-
tem water level. Check
ded.
the circulation pump.
Vent the heating sys-
tem. Check the tempe-
rature limiter and leads.
Press Reset .
The flame signal
Check the ionisation
is already present
electrode and leads.
at burner start.
Press Reset .