Viessmann Vitodens 222-F Installation And Service Instructions For Contractors page 60

Gas condensing storage combi boiler
Table of Contents

Advertisement

Codes
Coding level 1
(cont.)
Coding in the delivered condition
Min. flow temperature heating circuit
C5:20
Electronic minimum flow tempera-
ture limit 20 °C (only in operation
with standard room temperature;
only for weather-compensated
control units)
Max. flow temperature heating circuit
C6:74
Electronic maximum flow tempera-
ture limit 74 °C (only for weather-
compensated control units)
Heating program changeover
d5:0
With external heating program
changeover (observe setting for
coding addresses "3A", "3b" and
"3C" in the "General" group).
Operating program switches to
"Constant central heating with re-
duced room temperature" or
"Standby mode" (subject to the
settings of the set reduced room
temperature) (only for weather-
compensated control units).
Ext. heating program changeover to heating circuit
d8:0
With EA1 extension:
No operating program changeover.
Max. pump speed in standard mode
E6:...
Only for heating systems without a
heating circuit with mixer:
Maximum speed of the internal
speed-controlled heating circuit
pump in % of the max. speed in
standard mode. Value is specified
by boiler-specific parameters (only
for weather-compensated control
units).
Min. pump speed
E7:30
Only for heating systems without a
heating circuit with mixer:
Minimum speed of the internal
speed-controlled heating circuit
pump:
30 % of the max. speed (only for
weather-compensated control
units)
Screed drying
F1:0
Screed drying disabled (only for
weather-compensated control
units).
60
Possible change
C5:1
Minimum limit adjustable from 1 to
to
127 °C (limited by boiler-specific pa-
C5:127
rameters)
C6:10
Maximum limit adjustable from 10 to
to
127 °C (limited by boiler-specific pa-
C6:127
rameters)
d5:1
Heating program switches to "Con-
stant operation with standard room
temperature".
d8:1
Operating program changeover via
input DE1.
d8:2
Operating program changeover via
input DE2.
d8:3
Operating program changeover via
input DE3.
E6:0
Maximum speed adjustable from 0
to
to 100 %
E6:100
E7:0
Minimum speed adjustable from 0 to
to
100 % of the maximum speed
E7:100
F1:1
Only for heating circuit with mixer:
to
Screed drying adjustable, with
F1:6
choice of 6 temperature/time profiles
(see page 128)
F1:15
Constant flow temperature 20 °C