Troubleshooting
Fault codes
(cont.)
Fault code
Const.
displayed
b5
X
b7
X
b8
X
bA
bb
bC
bd
bE
bF
C1
X
84
Weather-
System characteris-
comp.
tics
X
Control mode as per
delivered condition
X
Burner blocked
X
Burner blocked
X
Mixer regulates to
20 °C flow tempera-
ture.
X
Mixer regulates to
20 °C flow tempera-
ture.
X
Control mode without
remote control
X
Control mode without
remote control
X
Control mode without
remote control
X
Control mode
X
Control mode
Cause
Measures
Internal fault
Replace the control unit
Boiler coding card
Plug in or replace the boil-
fault
er coding card.
Lead break, flue
Check the flue gas tem-
gas temperature
perature sensor (see
sensor
page 94).
Communication er-
Check the extension kit
ror, extension kit
connections and coding
for heating circuit 2
(with mixer)
Communication er-
Check the extension kit
ror, extension kit
connections and coding
for heating circuit 3
(with mixer)
Communication er-
Check connections, ca-
ror, Vitotrol remote
ble, coding address "A0"
control, heating cir-
in group "Heating cir-
cuit 1 (without mix-
cuit..."/5 and remote con-
er)
trol configuration (see
page 132).
For wireless remote con-
trols: Check connection,
place remote control unit
close to the boiler.
Communication er-
Check connections, ca-
ror, Vitotrol remote
ble, coding address "A0"
control, heating cir-
in group "Heating cir-
cuit 2 (with mixer)
cuit..."/5 and remote con-
trol configuration (see
page 132).
For wireless remote con-
trols: Check connection,
place remote control unit
close to the boiler.
Communication er-
Check connections, ca-
ror, Vitotrol remote
ble, coding address "A0"
control, heating cir-
in group "Heating cir-
cuit 3 (with mixer)
cuit..."/5 and remote con-
trol configuration (see
page 132).
For wireless remote con-
trols: Check connection,
place remote control unit
close to the boiler.
Incorrect LON
Replace LON communi-
communication
cation module
module
Communication er-
Check connections
ror, EA1 extension
Without EA1 extension:
Set code "5b:0" in group
"General"/1.