Viessmann Vitovalor 300-P Installation And Service Instructions For Contractors page 82

Micro chp unit based on a fuel cell with integral gas condensing boiler natural gas version
Hide thumbs Also See for Vitovalor 300-P:
Table of Contents

Advertisement

Commissioning, inspection, maintenance
2-yearly maintenance of fuel cell module
01. If these have not yet been actioned: Set service
mode (see page 75).
Note
The cooling process on the fuel cell module lasts
approximately 90 min. Only then should mainte-
nance work on the fuel cell module be started.
!
Please note
If this waiting time is not observed,
there is a risk of scalding and damage to
the appliance.
02. Remove the front panel of the fuel cell module and
programming unit cover
03. Select "01" using / .
04. Press SET.
"oFF" flashes.
05. Within the next 30 s select "on" using / .
06. Press SET.
The MNT indicator lights up. The fuel cell module
is in "Commissioning/maintenance" mode.
Replacing the distilled water filter element and air filter
Replace the distilled water filter element and air filter
every two years.
For parts, see page 163.
!
Please note
Take care to avoid injury from sharp edges.
Wear personal protective equipment (safety
gloves).
82
A
. See page 68.
(cont.)
07. Select "22" using / .
08. Press and hold SET for at least 3 s.
Under STATE, "01" and "02" appear in succes-
sion.
The water can be drained when "02" flashes.
09. Place a shallow container of sufficient size (min.
5 l) below drain ports
10. Undo the screw and remove right-hand cover
for ventilation.
11. Undo the screw in drain port
12. Remove plug
(do not remove screw
F
13. When no more water emerges and "04" is flash-
ing under STATE, close openings
again.
14. Press SET.
"End" and "nP" will appear alternately under
STATE.
Note
Never lubricate the gaskets.
.
B
C
approx. 1.5 turns.
D
).
E
,
and
C
D
F