Viessmann Vitovalor 300-P Installation And Service Instructions For Contractors page 119

Micro chp unit based on a fuel cell with integral gas condensing boiler natural gas version
Hide thumbs Also See for Vitovalor 300-P:
Table of Contents

Advertisement

Fault codes for gas condensing module
Fault code dis-
System characteristics
played
CF
Control mode
No communication via LON
d6
Control mode
d7
Control mode
d8
Control mode
dA
Control mode without room
influence
db
Control mode without room
influence
dC
Control mode without room
influence
dd
Control mode without room
influence
dE
Control mode without room
influence
dF
Control mode without room
influence
E0
Control mode
E1
Burner in a fault state
E2
Burner in a fault state
E3
Burner in a fault state
E4
Burner blocked
E5
Burner blocked
E6
Burner blocked
(cont.)
Cause
Communication error,
LON communication mod-
ule
Input DE1 at EA1 exten-
sion reports a fault.
Input DE2 at EA1 exten-
sion reports a fault.
Input DE3 at EA1 exten-
sion reports a fault.
Short circuit, room tem-
perature sensor, heating
circuit 1 (without mixer)
Short circuit, room tem-
perature sensor, heating
circuit 2 (with mixer)
Short circuit, room tem-
perature sensor, heating
circuit 3 (with mixer)
Lead break, room temper-
ature sensor, heating cir-
cuit 1 (without mixer)
Lead break, room temper-
ature sensor, heating cir-
cuit 2 (with mixer)
Lead break, room temper-
ature sensor, heating cir-
cuit 3 (with mixer)
External LON subscriber
error
Ionisation current too high
during calibration
Heat transfer too low dur-
ing calibration.
Heat transfer too low dur-
ing calibration.
Temperature limiter has
shut down.
24 V power supply fault
Flame amplifier fault
System pressure too low
Troubleshooting
Measures
Check LON communication mod-
ule and replace if required.
If no LON communication module
is installed, set code "76:0" in
"General" group.
Remedy fault at appliance con-
cerned.
Remedy fault at appliance con-
cerned.
Remedy fault at appliance con-
cerned.
Check room temperature sensor,
heating circuit 1.
Check room temperature sensor,
heating circuit 2.
Check room temperature sensor,
heating circuit 3.
Check room temperature sensor,
heating circuit 1 and remote control
configuration (see page 175).
Check room temperature sensor,
heating circuit 2 and remote control
configuration (see page 175).
Check room temperature sensor,
heating circuit 3 and remote control
configuration (see page 175).
Check connections and LON sub-
scribers.
Check gap between ionisation
electrode and burner gauze as-
sembly (see page 78).
In open flue operation, prevent
high levels of dust in the combus-
tion air.
Press reset R.
Ensure adequate heat transfer.
Press reset R.
Ensure adequate heat transfer.
Press reset R.
Replace control unit.
Replace control unit.
Top up with water.
119