Viessmann Vitovalor 300-P Installation And Service Instructions For Contractors page 101

Micro chp unit based on a fuel cell with integral gas condensing boiler natural gas version
Hide thumbs Also See for Vitovalor 300-P:
Table of Contents

Advertisement

Coding level 2
(cont.)
Coding in the delivered condition
52:0
Without flow temperature sensor
for low loss header
54:0
Never adjust.
6E:50
No display correction for outside
temperature
76:0
Without LON communication mod-
ule
77:1
LON subscriber number
79:1
Control unit for weather-compen-
sated operation with LON commu-
nication module:
Control unit is fault manager
7b:1
Control unit for weather-compen-
sated operation with LON commu-
nication module:
Control unit transmits the time
7F:1
Detached house
80:6
A fault message is issued if a fault
arises for at least 30 s.
81:1
Automatic summer/wintertime
changeover
82:0
Operation with natural gas
Possible change
The internal circulation pump only
starts upon heat demand if the burn-
er is active.
The circulation pump stops on expiry
of the run-on time.
51:2
System with heating water buffer
cylinder:
The internal circulation pump only
starts upon heat demand if the burn-
er is active.
The circulation pump stops on expiry
of the run-on time.
52:1
With flow temperature sensor for low
loss header (automatic recognition)
6E:0
Display correction
to
to
6E:49
Display correction
6E:51
Display correction +0.1 K
to
to
6E:99
Display correction +4.9 K
76:1
With LON communication module
(automatic recognition)
77:2
LON subscriber number adjustable
to
from 1 to 99:
77:99
1 - 4 = Boiler
27 = Fuel cell module
28 - 97 = Vitotronic 200-H
98 = Vitogate
99 = Vitocom
79:0
Control unit is not fault manager.
7b:0
No time transmission.
7F:0
Apartment building
Holiday program and time program
for DHW heating can be set sepa-
rately
80:0
Immediate fault message
80:2
Minimum fault duration before a fault
to
message is issued, adjustable from
80:199
10 to 995 s.
1 step
81:0
Manual summer/wintertime change-
over
81:2
Use of the radio clock receiver (au-
tomatic recognition)
81:3
With LON communication module:
Control unit receives the time
82:1
Operation with LPG (do not set)
Codes
5 K
0.1 K
5 s
101