Viessmann Vitovalor 300-P Installation And Service Instructions For Contractors page 107

Micro chp unit based on a fuel cell with integral gas condensing boiler natural gas version
Hide thumbs Also See for Vitovalor 300-P:
Table of Contents

Advertisement

Coding level 2
(cont.)
Coding in the delivered condition
A9:7
With pump idle time: heating circuit
pump "OFF" when set value is
modified by changing the operating
mode or changing the set room
temperature
b0:0
For heating circuit with mixer and
remote control only:
Heating mode/reduced mode:
Weather-compensated
b2:8
Only for heating circuit with mixer
and remote control. Operation with
room temperature hook-up must
be programmed for the heating cir-
cuit:
Room influence factor 8
b5:0
For heating circuit with mixer and
remote control only:
Without room temperature-de-
pendent heating circuit pump logic
function
Parameter address
With heating circuit pump logic function:
b5:...
Heating circuit pump "OFF"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
C5:20
Electronic minimum flow tempera-
ture limit 20 °C (only when operat-
ing at standard room temperature)
C6:74
Electronic maximum flow tempera-
ture limit 74 °C (only for weather-
compensated control units)
d3:14
Heating curve slope = 1.4
d4:0
Heating curve level = 0
RT
+ 5 K
>
actual
set
RT
+ 4 K
>
actual
set
RT
+ 3 K
>
actual
set
RT
+ 2 K
>
actual
set
RT
+ 1 K
>
actual
set
RT
>
actual
set
RT
1 K
>
actual
set
RT
2 K
>
actual
set
Possible change
A9:0
Without pump idle time
A9:1
With pump idle time, adjustable from
to
1 to 15.
A9:15
1 = short idle time
15 = long idle time
b0:1
Heating mode: Weather-compensa-
ted
Reduced mode: With room tempera-
ture hook-up
b0:2
Heating mode: With room tempera-
ture hook-up
Reduced mode: Weather-compen-
sated
b0:3
Heating mode/reduced mode: With
room temperature hook-up
b2:0
Without room influence
b2:1
Room influence factor adjustable
to
from 1 to 64. The higher the value,
b2:64
the greater the room influence.
b5:1
Heating circuit pump logic function,
to
see the following table.
b5:8
Heating circuit pump "ON"
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
Possible change
C5:1
Minimum limit adjustable from 1 to
to
127 °C (limited by boiler-specific pa-
C5:127
rameters)
C6:10
Maximum limit adjustable from 10 to
to
127 °C (limited by boiler-specific pa-
C6:127
rameters)
d3:2
Heating curve slope adjustable from
to
0.2 to 3.5 (see page 88)
d3:35
d4:–13
Heating curve level adjustable from
to
13 to 40 (see page 88)
d4:40
Codes
+ 4 K
+ 3 K
+ 2 K
+ 1 K
1 K
2 K
3 K
107