Viessmann Vitovalor 300-P Installation And Service Instructions For Contractors page 96

Micro chp unit based on a fuel cell with integral gas condensing boiler natural gas version
Hide thumbs Also See for Vitovalor 300-P:
Table of Contents

Advertisement

Codes
Coding level 1
(cont.)
Parameter address
With heating circuit pump logic function:
b5:...
Heating circuit pump "OFF"
1
RT
2
RT
3
RT
4
RT
5
RT
6
RT
7
RT
8
RT
Coding in the delivered condition
Min. flow temperature, heating circuit
C5:20
Electronic minimum flow tempera-
ture limit 20 °C (only when operat-
ing at standard room temperature)
Max. heating circuit flow temperature
C6:74
Electronic maximum flow tempera-
ture limit set to 74 °C
Heating program - changeover
d5:0
With external heating program
changeover. Observe settings of
coding addresses "3A", "3b" and
"3C" in "General" group.
Operating program switches to
"constant central heating with re-
duced room temperature" or
"standby mode" depending on the
setting of the reduced set room
temperature.
Ext. heating program changeover to heating circuit
d8:0
With EA1 extension:
No operating program changeover
Max. pump speed in standard mode
E6:...
Only for heating systems without a
heating circuit with mixer:
Max. speed of internal variable
speed heating circuit pump as % of
max. speed in standard mode. Val-
ue is specified by boiler-specific
parameters (only for weather-com-
pensated control unit).
96
RT
+ 5 K
>
actual
set
RT
+ 4 K
>
actual
set
RT
+ 3 K
>
actual
set
RT
+ 2 K
>
actual
set
RT
+ 1 K
>
actual
set
RT
>
actual
set
RT
1 K
>
actual
set
RT
2 K
>
actual
set
Heating circuit pump "ON"
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
RT
< RT
actual
set
Possible change
C5:1
Minimum limit adjustable from 1 to
to
127 °C (limited by boiler-specific pa-
C5:127
rameters)
C6:10
Maximum limit adjustable from 10 to
to
127 °C (limited by boiler-specific pa-
C6:127
rameters)
d5:1
Operating program switches to "con-
stant operation with standard room
temperature".
d8:1
Operating program changeover via
input DE1
d8:2
Operating program changeover via
input DE2
d8:3
Operating program changeover via
input DE3
E6:0
Maximum speed adjustable from 0
to
to 100 %
E6:100
+ 4 K
+ 3 K
+ 2 K
+ 1 K
1 K
2 K
3 K