Combustion Chamber Pressure Monitoring Function (Ldw2) - Viessmann MatriX Service Instructions For Contractors

Cylinder burner for natural gas e and ll
Table of Contents

Advertisement

Air pressure switch

Combustion chamber pressure monitoring function (LDW2)

A
B
Fig. 33
A
Reset button R
Air pressure switch 2
B
(cont.)
To monitor the combustion chamber pressure, the
switching threshold of air pressure switch 2 (LDW2) is
monitored in all operating phases (except during the
safety and stabilising time).
Air pressure switch
triggers a fault shutdown at the
C
burner control unit under the following circumstances:
If the combustion chamber pressure is outside the
permissible range in the pre-purge phase, in control
mode or in the post-purge phase after 2 attempts.
The fault shutdown is indicated by fault code "F FB"
on the burner control unit display. Reset the burner
control unit by pressing reset button R (
ter "Display and programming unit" on page 29.
Rated heat-
Rated heat in-
ing output
put
P
Q
(H
) [net
max
max
i
(50/30 °C)
cv]
in kW
400
500
630
Note
Check control cables:
Connection and kink-free routing
Application and seating of retaining clips
Functions
). See chap-
A
LDW2 setting value
in kW
in mbar (kPa)
381
474
5 (0.5)
593
43

Advertisement

Table of Contents
loading

This manual is also suitable for:

Proflame vm iv

Table of Contents