Viessmann MatriX Service Instructions For Contractors page 32

Cylinder burner for natural gas e and ll
Table of Contents

Advertisement

Burner control unit
Burner control unit
Resetting operating parameters to their delivered condition
Resetting operating parameters to their delivered con-
dition:
1. S longer than 2 s, " " flashes.
2.
until "6" is shown under Service.
3. S "6" is displayed under Status.
Manual mode and service indicator
To call up the service indicator and for manual opera-
tion the burner must be running. The service indicator
shows the current modulation level in %.
Press the following buttons:
1. /S simultaneously for longer than 2 s.
The burner switches to manual mode. "P"
appears on the display under Status and the
current modulation level flashes under Service.
32
(cont.)
4.
until "0" is shown under Service.
5. S "1" is shown under Status and "dEL" under Serv-
ice.
6. S to confirm. If reset successfully, "1" is shown
under Service; if it failed, "0" is shown.
7. S to change to the operating display.
2.
for the lower heating output, until "0" is shown
under Service.
3.
for the upper heating output, until "100" is
shown under Service.
4. /S simultaneously for longer than 2 s.
The burner returns to modulating mode.