Checking the burner gauze assembly
B
A
Fig. 18
Fig. 19
Replacing burner gauze assembly
2.
6x
1.
M12
Fig. 20
1. Check the wire mesh and cover of burner gauze
assembly
tions in burner gauze assembly
lematic.
2. Replace burner gauze assembly
3. Check seal
bly and thermal insulation. If necessary, replace
seal
assembly and the thermal insulation block with the
flame tube gasket.
1. Undo the burner frame from the boiler door.
A
2. Remove the flange gasket (scrape off if neces-
sary). Clean the sealing face.
3. Remove electrodes and burner gauze assembly.
4. Install the new burner gauze assembly with new
gasket for burner gauze assembly and electrodes.
Torque: 10 Nm
5. Mount the burner on the boiler door with new
flange gasket. Torque: 18 Nm
Commissioning, inspection, maintenance
(cont.)
A
for damage. Slight wavy deforma-
B
between the burner gauze assem-
. Seal the gap between the burner gauze
B
are not prob-
A
A
if required.