Viessmann MatriX Service Instructions For Contractors page 30

Cylinder burner for natural gas e and ll
Table of Contents

Advertisement

Burner control unit
Burner control unit
Status Service
Status Service
Status Service
Information display/configuration display
The information display and the configuration display
are activated from the operating display. For the menu
selection, press S and hold for longer than 2 s. You
can scroll through the menu points with / . To select a
menu point press S again. The relevant point is then
indicated under Service.
If no other button is pressed within 20 s, this mode is
automatically terminated.
Information regarding current meter readings, such as
the start-up meter and permanent hours run meter, can
be called up via the information display.
Information:
Menu
Description
point
1
Permanent meters for start-ups and
hours run
2
Resettable meters for start-ups and
hours run
3
Software version
4
Fault history for the last 10 fault codes
Example: To clear the hours run meter, press the fol-
lowing buttons:
1. S longer than 2 s, " " flashes.
2.
until "2" is shown under Service.
3. S "1" is displayed under Status.
30
(cont.)
Reheat
Post-purge
Dwell program, no air
pressure
Dwell program, no gas
pressure or
mains undervoltage
Status Service
Status Service
Status Service
4.
Scroll through Status until "6" is shown under
Status:
Status
Description
1
Display of resettable start-up me-
ter,1 digit
2
Display of resettable start-up me-
ter, 1000 digit
3
Menu point for deleting the start-up
meter reading
4
Display of resettable hours run me-
ter, 1 digit
5
Display of resettable hours run me-
ter, 1000 digit
6
Menu point for deleting the hours
run meter reading
5. S to confirm the deletion. If deleted successfully,
"1" is shown under Service; if it failed, "0" is
shown.
6. S to change to the operating display.
Menu points "5" and "6" are used to adjust configura-
tion settings of the burner control unit.
Note
Only make adjustments when the burner control unit is
on standby.
Configurations:
Menu
Description
point
5
Changeover from the operating display of the
burner control unit phase to other process in-
formation
6
Configuration of control function operating pa-
rameters
Forced ventilation if no
flame formation has been
detected.
Safety shutdown due to
flame tear-off
Safety shutdown when the
max. boiler water temper-
ature is reached