Checking The Static And The Supply Pressure - Viessmann MatriX Service Instructions Manual

Pressure−jet gas burner, for vitocrossal300, typect3 rated output 187 to 314kw
Table of Contents

Advertisement

Initial start−up, inspection and maintenance
Further details regarding the individual steps

Checking the static and the supply pressure

A
8
(cont.)
Static pressure
1. Close the gas shut−off valve.
2. Release the screw in the test
nipple A, but do not remove.
3. Release the pressure gauge in the
test nipple A, but do not remove.
4. Open the gas shut−off valve.
5. Check the static pressure
(max. 60 mbar).
6. Record the test value in the
service report (on page 49).