Viessmann MatriX Service Instructions For Contractors page 31

Cylinder burner for natural gas e and ll
Table of Contents

Advertisement

Burner control unit
Menu point "5" is used to display the following process information:
Sub-menu point
Process information
0
Phase
1
Not assigned
2
Flue gas temperature
3
Ionisation current
4
Set speed
5
PWM variable
6
Actual speed
7
Gas pressure switch 1
8
Gas pressure switch 2
9
Air pressure switch
A
Gas valve 1
B
Gas valve 2
Example: To display the ionisation current, press the
following buttons:
1. S longer than 2 s, " " flashes.
2.
until "5" is shown under Service.
Menu point "6" is used to change the following operating parameters:
Sub-
Parameter
menu
point
1
Maximum operational output
2
Gas type
3
Not assigned
4
Not assigned
5
Not assigned
6
Not assigned
0
Reset all operating parameters to their
delivered condition.
Example: To reduce the maximum operational output,
press the following buttons:
1. S
longer than 2 s, " " flashes.
2.
until "6" is shown under Service.
3. S
"6" is displayed under Status.
4. S
"1" is shown under Status and the current value
for the maximum operational output in % is
shown under Service.
(cont.)
Unit/scale
1
°C
I in 1/10
%
%
n in 10/min
0 or 1
0 or 1
0 or 1
0 or 1
0 or 1
3. S "5" is displayed under Status.
4.
until "3" is shown under Service.
5. S "3" is shown under Status; under Service the ion-
isation current is shown during operation (e.g.
30 = 3.0
A).
µ
Unit/scale
% of rated output
0 = NG (natural gas)
1 = Not assigned
5. /
for required maximum operational output.
Note
Observe the modulation range. See page 48.
6. S
to confirm. If adopted successfully, "1" appears
under Service; if it failed, "0" will appear.
7. S
to change to the operating display.
Burner control unit
A
μ
Delivered condition
100 %
0
31