Burner control unit VUC 310
Reset all operating parameters to their delivered condition
Reset all operating parameters to their delivered condi-
tion:
1. S for longer than 2 s.
flashes.
2.
until "6" is shown under Service.
3. S "6" will be displayed under Status.
Manual mode and service display
The burner must be running to call up the service dis-
play and for manual mode. The service display shows
the current modulation level in %.
Press the following keys:
1.
/S simultaneously for longer than 2 s.
The burner switches to manual mode. "P"
appears on the display under Status and the
current modulation level flashes under Serv-
ice.
2.
for the lower heating output to partial load
(0 %)
3.
The burner modulates upwards in 1 % steps
to full load (100 %)
4.
/S simultaneously for longer than 2 s.
The burner returns to modulating mode.
(cont.)
4.
5. S "1" is shown under Status and "dEL" under Serv-
6. S to confirm. If reset successfully, "1" will be shown
7. S To change to the operating display.
until "0" is shown under Service.
ice.
under Service; if not, "0" will appear.
Burner control unit
23