Viessmann MatriX Service Instructions For Contractors page 25

Pressure-jet gas burner for the vitocrossal 300, type ct3b rated heating output 187 to 314 kw
Table of Contents

Advertisement

Burner control unit flow diagram
Phase
Display
Relay test
"P"
Standby
"0"
Start-up
"1"
"2"
"3"
"4"
"5"
Operation
"6"
"7"
Shutdown
"8"
Waiting
"U"
"C"
Fault status
"9"
"10"
"11"
"F"
(cont.)
Description
Fan ramp-up for test
Safety relay test
Disabling relays BV1 and BV2
Relays BV1 and BV2 test
Ignition relay test
Disabling safety relay
Start-up meter, initialisation
Standby
Flame signal amplifier test
Gas fan and air pressure switch test
Fan ramp-up
Pre-purge
Adjusting start-up load, WD 1 test
Pre-ignition
Ignition safety time
Flame detection safety time
Flame stabilising time
Start-up, partial load
Modulating operation
Adjusting shutdown load
Reheating, WD 2 test
Fan ramp-up, post-purge
Post-purge
Waiting for restart
Waiting for mains gas pressure
Forced ventilation fault
Flame tear-off
Safety shutdown
Fault shutdown
Flow diagram
Duration
max. 20 s
0.9 s
0.9 s
0.9 s
0.9 s
0.9 s
0.1 s
0 ... s
max. 50 s
max. 20 s
max. 20 s
10 s
1.9 s
2 s
2.3 s
max. 0.51 s
15 s
20 s
0 to 24 h
0.1 s
min. 10 s,
max. 60 s
max. 20 s
10 s
1 min
5 min
20 s
0 ... s
0 ... s
0 ... s