Information display/configuration display

The information display and the configuration display
are activated from the operating display. The menu
selection is activated by pressing and holding S for
longer than 2 s. You can scroll through the menu
points with / . To select a menu point press S again.
The relevant point is then shown on the display under
Service.
This mode is automatically terminated if no other key is
pressed within 20 s.
Information regarding current meter readings, such as
the start-up meter and permanent hours run meter, can
be called up via the information display.
Information:
Menu
Description
point
1
Permanent meters for start-ups and hours
run
2
Meters for start-ups and hours run with re-
set
3
Software version
4
Fault history for the last 10 fault codes
(cont.)
Dwell program, no air pressure
Dwell program, no gas pressure or mains undervoltage
Forced ventilation if no flame formation has been
detected
Safety shutdown due to flame tear-off
Example – resetting the hours run meter:
1. S for longer than 2 s,
2.
3. S "1" will be displayed under Status.
4.
flashes.
until "2" is shown under Service.
Scroll through Status until "6" is shown under
Status:
Status
Description
1
Display of resettable start-up meter,
1 digit
2
Display of resettable start-up meter,
1000 digit
3
Menu point for deleting the start-up
meter reading
4
Display of resettable hours run meter,
1 digit
5
Display of resettable hours run meter,
1000 digit
6
Menu point for deleting the hours run
meter reading