Viessmann MatriX Service Instructions For Contractors page 12

Pressure-jet gas burner for the vitocrossal 300, type ct3b rated heating output 187 to 314 kw
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Checking the CO
2. Start the burner with the emissions test switch ena-
bled.
CO
test at the upper heating output
2
1. Press and hold
until the service display has
F
counted up to "100" (= 100 %).
2. Check the CO
content in the flue pipe.
2
Burner output in kW
187
248
314
CO
test at the lower heating output
2
B
A
Fig. 9
12
content
(cont.)
2
Permissible CO
con-
2
tent in %
9.0 (+0.3/-0.1)
3. Simultaneously press and hold S
longer than 2 s.
Display
will then show the following:
C
Under Status: "P" (= controlled stop)
Under Service: Modulation level in %
("100" = 100 % = upper heating output,
"0" = 0 % = lower heating output)
3. If the CO
content needs to be adjusted:
2
Remove cap
B
and turn setting screw
steps (Allen key 3 mm) until the CO
within the specified range:
Turning clockwise
Turning anticlockwise
4. Record the actual value in the report (on
page 38).
C
D
E
F
Fig. 10
1. Press and hold
until the service display has
D
counted down to "0" (lower heating output).
E
and
D
for
A
in small
content is
2
CO
content drops
2
CO
content increases
2