Gree NCHS2D Owner's Manual page 26

Commercial air conditioners. gmv6 hr mode exchange box
Hide thumbs Also See for NCHS2D:
Table of Contents

Advertisement

4.2.7 Size Requirement for Branch Pipe and Piping
Take the connection sketch map of single-module system for example.
4.2.7.1 Branch Selection of Mode Exchange Box ("A1, A2")
Select branch of Mode Exchange Box as per total capacity of downstream indoor unit(s).
Please refer to the following table.
Model selection for branch "A1、A2" of Mode Exchange Box;
R410A refrigerant system
Y-Type Branch Pipe
4.2.7.2 Connection for Single Indoor Unit with Capacity of less than 16kW
Piping size among downstream branches of Mode Exchange Box "a、h、l"
Total rated capacity of downstream
indoor units: X (kW)
X≤2.8
2.8<X≤5
5<X≤14
14<X≤16
Each branch is to connect to a set of indoor units with the same mode. For the branch does not
connect to indoor unit, make sure that the welding is reliable without leaking of refrigerant.
Branch selection of downstream indoor unit of Mode Exchange Box ("B1、B2、B3")
Fig.4.2.16
Total capacity of the downstream indoor unit X(kW)
X≤5
5<X≤22.4
22.4<X≤28
28<X≤68
68<X≤96
96<X
Piping size among downstream branches of Mode Exchange Box
Gas pipe/mm
Φ9.52
Φ12.7
Φ15.9
Φ19.05
22
GMV6 HR Mode Exchange Box
Model
FQ01Na/A
FQ02Na/A
FQ03Na/A
FQ04Na/A
FQ05Na/A
FQ06Na/A
Liquid pipe/mm
Φ6.35
Φ6.35
Φ9.52
Φ9.52

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nchs4dNchs8d

Table of Contents