PROFIBUS-DP und das PROFIBUS-Logo sind eingetragene Warenzeichen der PROFIBUS Nutzerorganisation e.V. (PNO) SIMATIC ist ein eingetragenes Warenzeichen der SIEMENS AG TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 2 of 115 TR - ECE - BA - DGB - 00036 - 10...
8.2 PNO CLASS 1 16-Bit ......................26 8.3 PNO CLASS 1 32-Bit ......................26 8.4 PNO CLASS 2 16-Bit ......................27 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Page 4
9.2.2.17 Seriennummer ......................... 56 9.2.2.18 Herstellerspezifische Diagnosen ..................... 57 9.3 Sonstige Störungen ........................ 57 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 4 of 115 TR - ECE - BA - DGB - 00036 - 10...
Zusätzliche Hinweise für Auflösungen > 13 Bit 10.01.11 Anpassung der Warnhinweise 20.09.11 Neues Design 01.10.14 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 5 of 115...
Benutzerhandbuch, und die bei der Lieferung beiliegende Montageanleitung TR-ECE-BA-DGB-0035 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 6 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
das Beachten der Montageanleitung, insbesondere das dort enthaltene Kapitel "Grundlegende Sicherheitshinweise" muss vor Arbeitsbeginn gelesen und verstanden worden sein TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 8 of 115 TR - ECE - BA - DGB - 00036 - 10...
Dies gilt in besonderem Maße für nur gelegentlich, z. B. bei der Parametrierung des Mess-Systems, tätig werdendes Personal. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Störaussendung: ........DIN EN 61000-6-3: 2007 * parametrierbar über den PROFIBUS-DP TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 10 of 115 TR - ECE - BA - DGB - 00036 - 10...
Datenaustausch in der Feldebene konzipiert ist. Die Grundfunktionalität wird durch die Leistungsstufe V0 festgelegt. Dazu gehören der zyklische Datenaustausch sowie die stations-, modul- und kanalspezifische Diagnose. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014...
Richtlinien und sonstige einschlägige Normen und Richtlinien zu beachten! Insbesondere sind die EMV-Richtlinie sowie die Schirmungs- und Erdungsrichtlinien in den jeweils gültigen Fassungen zu beachten! TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 12 of 115...
Die Klemmen für die Versorgungsspannung (Pin 3 / Pin 4) sind intern miteinander verbunden und können sowohl als Einspeisung, als auch für die Versorgung des nachfolgenden Teilnehmers verwendet werden. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014...
80 mm X mm Das Maß "X" ist abhängig vom Typ und Größe der verwendeten Kabelverschraubung. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 14 of 115 TR - ECE - BA - DGB - 00036 - 10...
Page 15
6. Dichteinsatz / Kontakthülse (2) + (3) in Einschraubstutzen (5) bündig zusammen stecken. 7. Überwurfmutter (1) mit Einschraubstutzen (5) verschrauben. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Page 16
Einschraubstutzen vorgesehenen Längsnuten passen. 7. Überwurfmutter (1) mit Einschraubstutzen (4) verschrauben. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 16 of 115 TR - ECE - BA - DGB - 00036 - 10...
Stationsadresse läuft das Gerät nicht. 5.3.4 Schirmauflage Die Schirmung ist großflächig auf den Gegenstecker aufzulegen. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 18 of 115 TR - ECE - BA - DGB - 00036 - 10...
Projektierungsfehlern erreicht. Das Mess-System hat die PNO-Identnummer AAAB (Hex). Diese Nummer ist reserviert und bei der PNO hinterlegt. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
WCFG = Wait Configuration DXCHG = Data Exchange Abbildung 4: DP-Slave Initialisierung TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 20 of 115 TR - ECE - BA - DGB - 00036 - 10...
Mess-System Störung Entsprechende Maßnahmen im Fehlerfall siehe Kapitel „Störungsbeseitigung und Diagnosemöglichkeiten“, Seite 49. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
0 = Konsistenz über ein Byte oder Wort Konsistenz: 1 = Konsistenz über das ganze Modul TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
- Oberer Endschalter Geschwindigkeits-Ausgabe - Geschwindigkeit aus Sicht des Bus-Masters TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 24 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Geschwindigkeits-Ausgabe - Oberer Endschalter - Geschwindigkeit aus Sicht des Bus-Masters TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 25 of 115...
0: steigende Werte [x] Zählrichtung Bit 0 1: fallende Werte TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 26 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Messlänge in Gesamtmesslänge in Schritten Unsigned32 Schritten Default = 16777216 Schritte TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 27 of 115...
Messlänge in Gesamtmesslänge in Schritten Unsigned32 Schritten Default = 16777216 Schritte TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 28 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Unsigned32 Default = 4096 Datenbits SSI-Schnittstelle Unsigned8 wird nicht unterstützt TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 29 of 115...
Umdrehungen Zähler Unsigned32 Default = 4096 (Zähler) Fortsetzung siehe Folgeseite TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 30 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Page 31
Auflösung der Geschwindigkeitsausgabe Geschwindigkeit Unsigned8 Default = 1 (1 Digit = 1 Umdr./min) TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 31 of 115...
Positionswert für oberen Endschalter 17-20 Oberer Endschalter Unsigned32 Default = 4096 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 32 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Auflösung der Geschwindigkeitsausgabe Geschwindigkeit Unsigned8 Default = 1 (1 Digit = 1 Umdr./min) TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 33 of 115...
Im CLASS 2 Mode erfolgt keine Quittierung des Vorgangs über die Eingänge. Untergrenze programmierte Gesamtmesslänge in Schritten – 1 Obergrenze TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 34 of 115 TR - ECE - BA - DGB - 00036 - 10...
Wertesprünge > 1 Umdrehung) einen "Diagnosealarm" (OB82 bei SIMATIC auslöst, siehe auch Kapitel "Alarme", Seite 53. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
–2 ohne Bedeutung Preset-Justagewert –2 Preset-Justagewert –2 Preset-Justagewert –2 Preset-Justagewert TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 36 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Mit diesem Parameter kann die Anzahl der Diagnosebytes von 6+51 Bytes auf 6+10 Bytes begrenzt werden, damit das Mess-System auch an PROFIBUS-Mastern mit älteren Ausgabeständen betrieben werden kann. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014...
Obergrenze 8192 Schritte pro Umdrehung (Max.-Wert siehe Typenschild) Default 4096 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 38 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Richtung fahren, zwangsläufig zu Verschiebungen. Für derartige Anwendungen ist stets eine der TR-Konfigurationen "TR-Mode..." zu verwenden. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Zur Berechnung können die Parameter Schritte/Umdr. und Anzahl Umdrehungen vom Typenschild des Mess-Systems abgelesen werden. ergibt sich indirekt über die Parameter Messlänge in Schritten und Umdrehungen Zähler/Nenner TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 40 of 115...
Mess-System bei einer geringfügigen Überschreitung des Verfahrweges keinen Istwertsprung (Nullübergang) erzeugt. Der Einfachheit halber kann auch der volle Umdrehungsbereich des Mess-Systems programmiert werden. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Page 42
= 1348,073499 Schritte / Umdr. * 1 Umdrehung Nenner = 5521709 Schritte (abgerundet) TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 42 of 115 TR - ECE - BA - DGB - 00036 - 10...
Umdrehungsgeschwindigkeit wird als 2er-Komplement ausgegeben. CW = positiv, CCW = negativ mit Blick auf die Anflanschung. Default = 1 U/min. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Preset-Ausführung mit steigender Flanke, siehe Seite 34 –2 Preset-Justagewert –2 Preset-Justagewert –2 Preset-Justagewert –2 Preset-Justagewert TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 44 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Dateinamen und Einträge in den nachfolgenden Masken sind nur als Beispiele für die Vorgehensweise zu betrachten. Zur Aufnahme der GSD-Datei in den Katalog, muss diese zuerst installiert werden: TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014...
Page 46
Seite 33 Der Eintrag Universalmodul wird irrtümlicherweise automatisch von manchen Systemen bereitgestellt, darf jedoch nicht verwendet werden! TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 46 of 115 TR - ECE - BA - DGB - 00036 - 10...
Page 47
Netzeinstellungen vorgenommen werden (Klick mit rechter Maustaste auf das Mess- System-Symbol --> Objekteigenschaften): TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Page 48
Gewünschte Konfiguration aus dem Katalog auf den Steckplatz übertragen (Drag&Drop). Das Mess-System-Symbol muss aktiv sein. Parametrierung vornehmen mit Doppelklick auf die Steckplatznummer: TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 48 of 115...
Gültiger Preset-Vorwahlwert = programmierte Gesamtmesslänge in Schritten – 1 Mess-System läuft nicht am Bus TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Byte 8 gerätespezifische weitere gerätespezifische Diagnose Erweiterungen Byte 241 (max) TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 50 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Überlauf bei erweiterter Bit 7 Ext_Diag_Overflow Diagnose Bit 6-0 Reserviert TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 51 of 115...
Stehen zusätzliche Diagnoseinformationen zur Verfügung, so trägt der Slave an dieser Stelle die Anzahl der Bytes ein, die außer der Normdiagnose noch folgen. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 52 of 115...
Bit 6 nicht benutzt Bit 7 nicht benutzt TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 53 of 115...
Für zusätzliche Alarme ist das Byte 17 reserviert, jedoch sind keine weiteren Alarme implementiert. Erweiterte Diagnose, Byte 17 Bedeutung Bit 0-7 reserviert TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 54 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Erweiterte Diagnose, Byte 24-25 Byte 24 Revisions-Nummer Byte 25 Revisions-Index TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 55 of 115...
Erweiterte Diagnose, Byte 48-57 Die Diagnosebytes zeigen Seriennummer des Encoders an. Wird diese Funktion nicht unterstützt, werden Sterne angezeigt (Hex-Code 0x2A) **********. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 56 of 115...
Störung, wenn die vertauscht Bushaube auf das Mess-System gesteckt wird TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 57 of 115...
Page 58
Störungsbeseitigung und Diagnosemöglichkeiten TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 58 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Page 59
User Manual Cxx-58 PROFIBUS-DP TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 59 of 115...
Page 60
PROFIBUS-DP and the PROFIBUS logo are registered trademarks of PROFIBUS Nutzerorganisation e.V. (PNO) [PROFIBUS User Organization] SIMATIC is a registered trademark of SIEMENS corporation TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 60 of 115...
8.2 PNO CLASS 1 16-Bit ......................84 8.3 PNO CLASS 1 32-Bit ......................84 8.4 PNO CLASS 2 16-Bit ......................85 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Page 62
9.2.2.17 Serial number .......................... 114 9.2.2.18 Manufacturer's diagnoses ....................... 115 9.3 Other faults ..........................115 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 62 of 115 TR - ECE - BA - DGB - 00036 - 10...
Additional hints in case of resolutions > 13 bit 01/10/11 Modification of the warnings 09/20/11 New Design 10/01/14 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 63 of 115...
and the assembly instructions TR-ECE-BA-DGB-0035, which is enclosed when the device is delivered TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 64 of 115 TR - ECE - BA - DGB - 00036 - 10...
Device Master File PROFIBUS User Organization (PROFIBUS Nutzerorganisation) PROFIBUS Manufacturer independent, open field bus standard TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
observing the assembly instructions. The "Basic safety instructions" in particular must be read and understood prior to commencing work. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 66 of 115 TR - ECE - BA - DGB - 00036 - 10...
This particularly applies for personnel who are only deployed occasionally, e.g. at the parameterization of the measurement system. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Transient emissions: ........DIN EN 61000-6-3: 2007 * parameterizable via PROFIBUS-DP TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 68 of 115 TR - ECE - BA - DGB - 00036 - 10...
The basic functionality is defined by the performance level V0. This includes cyclic data exchange, as well as the station, module and channel-specific diagnosis. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014...
In particular, the applicable EMC directive and the shielding and grounding guidelines must be observed! TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 70 of 115...
The terminals for the supply voltage (pin 3 / pin 4) are connected together internally and can be used as feeding, as well as supply voltage for the subsequent slave. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany...
80 mm X mm The dimension "X" depends on the type and size of the cable gland. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 72 of 115 TR - ECE - BA - DGB - 00036 - 10...
Page 73
6. Push seal / contact bush (2) + (3) flush into the screw socket (5). 7. Screw the nut (1) to the screw socket (5). TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014...
Page 74
6. Insert the clamping ring (2) in the screw socket (4) such that the torque supports fit in the slots in the screw socket (4). 7. Screw the nut (1) to the screw socket (4). TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 74 of 115...
Mating connector for X2 Male cable connector LUMBERG: 0976 PMC 101 Male cable connector PHOENIX CONTACT: 15 07 76 4 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
5.3.4 Shield cover The shielding is to be connected with large surface on the mating connector. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 76 of 115 TR - ECE - BA - DGB - 00036 - 10...
The measuring system has the PNO ID number AAAB (hex). This number is reserved and is stored at the PNO. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
WCFG = Wait Configuration DXCHG = Data Exchange Figure 4: DP slave initialization TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 78 of 115 TR - ECE - BA - DGB - 00036 - 10...
Non-recoverable measuring system fault Corresponding measures in case of an error see chapter “Troubleshooting and diagnosis options”, page 107. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Denominator lower limit: 1 Denominator upper limit: 99 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 80 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
0 = Consistency about one byte or word Consistency: 1 = Consistency about the complete module TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
- Upper limit switch Velocity output - Velocity from the bus master perspective TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 82 of 115 TR - ECE - BA - DGB - 00036 - 10...
Velocity output - Upper limit switch - Velocity from the bus master perspective TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 83 of 115...
0: increasing values [x] Count direction Bit 0 1: decreasing values TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 84 of 115 TR - ECE - BA - DGB - 00036 - 10...
Total measuring range in steps Unsigned32 range Default = 16777216 steps TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 85 of 115...
Total measuring range in steps Unsigned32 range Default = 16777216 steps TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 86 of 115 TR - ECE - BA - DGB - 00036 - 10...
Unsigned32 Default = 4096 Data bits SSI-Interface Unsigned8 not supported TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 87 of 115...
Revolutions numerator Unsigned32 Default = 4096 (numerator) Continuation see following page TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 88 of 115 TR - ECE - BA - DGB - 00036 - 10...
Page 89
Resolution of the speed output Velocity Unsigned8 Default = 1 (1 Digit = 1 revol./min) TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Position value for upper limit switch 17-20 Upper limit switch Unsigned32 Default = 4096 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 90 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Resolution of the speed output Velocity Unsigned8 Default = 1 (1 Digit = 1 revol./min) TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Lower limit programmed total measuring length in increments – 1 Upper limit TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 92 of 115 TR - ECE - BA - DGB - 00036 - 10...
SIMATIC S7) for an internal error (memory or value jump > 1 revolution), also see Chapter "Alarms", page 111. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
Preset adjustment value –2 Preset adjustment value –2 Preset adjustment value TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 94 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
The number of diagnosis bytes can be restricted from 6+51 bytes to 6+10 bytes with this parameter, such that the measuring system can also be operated with older PROFIBUS master releases. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014...
8192 steps per revolution (Max. value see nameplate) Upper limit Default 4096 TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 96 of 115 TR - ECE - BA - DGB - 00036 - 10...
For such applications, one of the TR configurations "TR-Mode…" are always to be used. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
To calculate, the parameters Steps per revolution and the Number of revolutions can be read on the measuring system nameplate. results indirectly by the parameters Total measuring range and Revolutions numerator/denominator TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 98 of 115...
(zero transition) if the distance travelled is exceeded. To simplify matters the complete revolution range of the measuring system can also be programmed. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014...
Page 100
= 1348.073499 steps / rev. * 1 revolution denominator = 5521709 steps (rounded off) TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 100 of 115 TR - ECE - BA - DGB - 00036 - 10...
1/1 and 1/100 rpm. The rotational speed is output as two's complement value. CW = positive, CCW = negative, with view onto the flange connection. Default = 1 rpm. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014...
Preset adjustment value –2 Preset adjustment value –2 Preset adjustment value TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 102 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
File names and entries in the following masks are to be regarded only as examples of the procedure. For the GSD file to be transferred to the catalogue, it must first be installed: TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014...
Page 104
91 The entry Universal module is erroneously available for some systems, but must not be used! TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 104 of 115 TR - ECE - BA - DGB - 00036 - 10...
Page 105
Connect measuring system to the master system (drag&drop): Once the measuring system is connected to the master system, the network settings can be undertaken --> Object Properties... --> PROFIBUS... button): TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014...
Page 106
Transfer the required configuration from the catalogue to the slot (drag&drop). The measuring system symbol must be active. Perform parameterization with a double click on the slot number: TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 106 of 115...
– 1 measuring range. The measuring system is not running at the bus. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10...
8 device-specific further device-specific diagnosis extensions byte 241 (max) TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 108 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
7 Ext_Diag_Overflow Overrun for extended diagnosis bit 6-0 Reserved TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 109 of 115...
If further diagnosis information’s are available, the slave enters the number of bytes at this location, which follow in addition to the standard diagnosis. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 110 of 115...
6 not used bit 7 not used TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 111 of 115...
Byte 17 is reserved for additional alarms, however no further alarms are implemented. Extended diagnosis, byte 17 Significance bit 0-7 reserved TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 112 of 115 TR - ECE - BA - DGB - 00036 - 10 10/01/2014...
Extended diagnosis, bytes 24-25 byte 24 Revision number byte 25 Revision index TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 113 of 115...
The diagnosis bytes show the serial number of the encoder. If this function is not supported, asterisks ********** (hex code 0x2A) are displayed. TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany Page 114 of 115...
TR-Electronic GmbH 2004, All Rights Reserved Printed in the Federal Republic of Germany 10/01/2014 TR - ECE - BA - DGB - 00036 - 10 Page 115 of 115...