Parameter
UI Display Remarks
Number of
05 NO.
batteries
Total battery
06 CAP
capacity
Charge
07 CL
current limit
Start
Set the output voltage level.
Set the output frequency system.
UPS with standard backup time?
Yes
Check that the input is normal
On the default screen, hold down
hear a beep tone.
After you ensure that the UPS runs properly, close the AC output circuit breakers on the rear
panel of the UPS (only for professional version), close the UPS AC output circuit breaker to
supply power to the loads.
The following figures show the parameter setting screen for a 10 kVA standard UPS with long
backup time working in normal mode.
Set the number of batteries based on the actual battery quantity.
• Professional version with standard backup time: 20 batteries; standard
version with standard backup time: 16 batteries, not configurable
• UPS with long backup time: 16 batteries by default; value range: 16–
20
Set this parameter to the total capacity of all batteries actually connected.
• 6 kVA UPS with standard backup time: 7 Ah, not configurable; 10 kVA
UPS with standard backup time: 9 Ah, not configurable
• 6 kVA UPS with long backup time: 40 Ah by default; 10 kVA UPS with
long backup time: 65 Ah by default; value range: 7–999 Ah
• Set this parameter to the maximum charge current in equalized charge
mode based on actual conditions.
• 6 kVA or 10 kVA UPS with standard backup time: 2 A, not configurable
• 6 kVA or 10 kVA UPS with long backup time: 4 A by default; value
range: 1–8 A, at an interval of 0.5 A
for more than 5 seconds. Release the button when you
End
No: UPS with long
backup time
8
Set the number of batteries.
Set the total battery capacity.
Set the charge current limit.