Huawei UPS2000-A-6KTTS-S Quick Manual page 5

Hide thumbs Also See for UPS2000-A-6KTTS-S:
Table of Contents

Advertisement

Model
Wiring Terminal
External Circuit Breaker
Earth Leakage Circuit Breaker
Cable Cross-sectional Area
Terminal Type
6 kVA/10 kVA Standard Version
with Standard Backup Time
UPS2000-A-6KTTS-S
M4 (6 PCS)
1.4 N•m
Mains
6 kVA/10 kVA Professional Version
with Standard Backup Time
UPS2000-A-6KTTS-P
M4 (6 PCS)
1.4 N•m
Mains
1. For a single UPS, install a short-circuit bar between JP1 and JP2. For a parallel system, do not
install it. When transferring from single mode to parallel mode, confirm that the short-circuit
bar is removed.
2. The professional version supports the dual-live wire system. Connect the L1 and L2 wires
respectively to the L and N terminals on the UPS.
UPS2000-A-6KTTS-S
UPS2000-A-6KTTL-S
UPS2000-A-6KTTS-P
UPS2000-A-6KTTL-P
AC INPUT
50 A/D
100 mA
6 mm
2
OT-6 mm
2
-M4 terminal
UPS2000-A-10KTTS-S
M5 (6 PCS)
2.8 N•m
AC
load
UG10000016
UPS2000-A-10KTTS-P
M5 (6 PCS)
2.8 N•m
Short-
circuit
bar
AC
Mains
load
UG10000090
AC OUTPUT
-
6 kVA/10 kVA Standard Version
UPS2000-A-6KTTL-S
M4 (6 PCS)
1.4 N•m
Mains
6 kVA/10 kVA Professional Version
UPS2000-A-6KTTL-P
M4 (6 PCS)
1.4 N•m
4
UPS2000-A-10KTTS-S
UPS2000-A-10KTTL-S
UPS2000-A-10KTTS-P
UPS2000-A-10KTTL-P
AC INPUT
AC OUTPUT
63 A/D
100 mA
-
10 mm
2
OT-10 mm
2
-M6 terminal
with Long Backup time
UPS2000-A-6KTTL-S
M5 (6 PCS)
2.8 N•m
with Long Backup Time
UPS2000-A-6KTTL-P
M5 (6 PCS)
2.8 N•m
UG10000089
AC
load
Short-
circuit
bar
AC
load