Huawei UPS2000-A-6KTTS-S Quick Manual page 21

Hide thumbs Also See for UPS2000-A-6KTTS-S:
Table of Contents

Advertisement

Alarm
Alarm Name
ID
Maintenance
circuit
3B
breaker ON
Internal fault
2A
Parallel
settings
43
abnormal
Bypass
47
backfeed
Parallel
cables
53
abnormal
Parallel cable
54
alarm
EPO
55
Insufficient
5E
redundancy
Parallel
parameter
7D
inconsistency
Alarm
Cause
Repair Proposal
ID
Possible cause: The maintenance bypass switch is ON during
UPS maintenance.
1
Measure: Set the maintenance bypass switch to OFF after
maintenance.
• Possible cause: The mains has experienced a transient high
voltage.
Measure: Rectify the fault and restart the UPS.
• Possible cause: The output supplies power to special loads
11
such as the inductive and rectification loads.
Measure: Check that the load types are supported by the
UPS.
• Possible cause: The hardware is damaged.
Measure: Contact Huawei technical support.
Possible cause: The single UPS or parallel system settings are
1
inconsistent with the system cable connections.
Measure: Check the single UPS and parallel system settings.
Possible cause: Bypass components are faulty.
1
Measure: Contact Huawei technical support.
1
• Possible cause: The parallel cables connected are loose.
2
Measure: Check that parallel cables are securely connected.
• Possible cause: Parallel cables are damaged.
4
Measure: Replace the parallel cables.
5
• Possible cause: The parallel cables connected are loose.
2
Measure: Check that parallel cables are securely connected.
• Possible cause: The parallel cables are damaged.
3
Measure: Replace the parallel cables.
Possible cause: You have pressed the EPO switch.
1
Measure: Restore the EPO switch status, clear the alarm, and
restart the UPS.
• Possible cause: The number of redundant UPSs is too large.
Measure: Reduce the number of redundant UPSs or set the
UPS to work in non-redundant mode.
1
• Possible cause: The load exceeds the rated loading capacity
of the UPSs that are working in the parallel system.
Measure: Lower the load or replace the UPS with a UPS
with a larger capacity.
Possible cause: Parallel parameters are inconsistent between
1
UPSs in the parallel system.
Measure: Manually synchronize parallel parameters.