5
Verifying the Installation
1. Refer to chapter
4 "Verifying the Installation"
before power-on. For details, see page 6.
2. Check that the parallel communications cables are properly connected.
6
Powering On and Starting the UPS
1. Do not start loads before the parallel system is started.
2. Before power-on and startup, ensure that each branch output circuit breaker is closed and the
outputs are connected in parallel.
Powering On the UPS
6.1
Check that the UPS has passed all check items described in
chapter
5 "Verifying the Installation".
Close the external battery circuit breakers (if there are).
Start the UPS in normal mode?
Close the general AC input circuit breaker for UPSs, each
branch input circuit breaker, and the AC input circuit breakers
on the rear panels of UPS 1 and UPS 2.
Close each branch output circuit breaker.
Check that the voltage is normal.
Setting Key UPS Parameters
6.2
1. Refer to section
5.2 "Setting Key UPS Parameters"
UPS. For details, see page 7.
2. Set the parallel mode and the number of redundant UPSs.
Start
Yes
End
to check each UPS in the parallel system
No: Start the UPS in battery mode.
to set system and battery parameters for each
12