Installing Battery Cables (Only for UPS with Long Backup Time)
1. A UPS with long backup time is connected to external battery strings. Each battery string
consists of 16 to 20 batteries (16 by default, configurable).
2. Install a DC circuit breaker between a battery string and the UPS with long backup time.
Install a 50 A 300 V DC circuit breaker for the 6 kVA model, and a 63 A 300 V DC circuit
breaker for the 10 kVA model.
3. One or two battery boxes can be connected. For details, see the ESS-240V12-2x(9AhBPVBA,
7AhBPVBA) Quick installation Guide. If longer backup time is required, choose a battery rack.
Connecting External Battery Strings
Model
Wiring Terminal
External Circuit Breaker
Cable Cross-sectional Area
Terminal Type
UPS2000-A-6KTTS-P
M4 (3 PCS)
1.4 N•m
Connecting External Battery Boxes
UPS
UPS2000-A-6KTTL-S
UPS2000-A-6KTTL-P
BATT.
50 A
6 mm
2
OT-6 mm
UPS2000-A-10KTTS-P
M5 (3 PCS)
2.8 N•m
UPS battery box 1
BATT.PORT/240VDC
PE
-
+
-M4 terminal
2
Ground
UPS
BATT.PORT/240VDC
BATT.PORT/240VDC
PE
-
+
5
UPS2000-A-10KTTL-S
UPS2000-A-10KTTL-P
BATT.
63 A
10 mm
2
OT-10 mm
-M6 terminal
2
Battery 1
Battery 1
point
Battery 20
Battery 20
External battery strings
UG10000091
battery
box 2
BATT.PORT/240VDC
PE
PE
-
+
UG10000092