Error Messages (3 of 3)
The error messages listed below for RTU 1 will be the same for RTU 2, RTU 3, RTU 4, RTU 5 and RTU 6.
Error Displayed
The warning message listed below for ROOM 1 will be the same for ROOM 2, ROOM 3, ROOM 4, ROOM 5 and ROOM 6.
The control is no longer able to read the information that is coming from RTU 1. Reconnect RTU 1
and press either the Menu or Item button to clear the error. If the RTU has been deliberately
disconnected from the control, remove power from the control for 10 seconds and then repower
the control in order to clear the error messasge.
The Remote 1 Sensor attached to RTU 1 is being read as a short circuit. RTU 1 will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if RTU 1 was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D
070e. To clear the error message from the control, press either the Menu or Item button.
REMOTE 1 ≠ NONE.
The Remote 1 Sensor attached to RTU 1 is being read as an open circuit. RTU 1 will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if RTU 1 was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D
070e. To clear the error message from the control, press either the Menu or Item button.
REMOTE 1 ≠ NONE.
The Remote 2 Sensor attached to RTU 1 is being read as a short circuit. RTU 1 will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if RTU 1 was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D
070e. To clear the error message from the control, press either the Menu or Item button.
REMOTE 2 ≠ NONE.
The Remote 2 Sensor attached to RTU 1 is being read as an open circuit. RTU 1 will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if RTU 1 was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D
070e. To clear the error message from the control, press either the Menu or Item button.
REMOTE 2 ≠ NONE.
The Remote 3 Sensor attached to RTU 1 is being read as a short circuit. RTU 1 will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if RTU 1 was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D
070e. To clear the error message from the control, press either the Menu or Item button.
REMOTE 3 ≠ NONE.
The Remote 3 Sensor attached to RTU 1 is being read as an open circuit. RTU 1 will continue
operation using all remaining sensors. If all of the sensors are unavailable, the control will continue
to operate as if RTU 1 was not connected to the control. This error message can be cleared once
the sensor has been repaired. Locate and repair the problem as described in the Data Brochure D
070e. To clear the error message from the control, press either the Menu or Item button.
REMOTE 3 ≠ NONE.
Cooling control is selected but there is no display RTU connected to the tN1 6 terminal. The control
will continue to operate as if COOL MOD was set to NONE. To clear the error message from the
control, press either the Menu or Item button.
This warning message will be displayed if the air temperature sensed by RTU 1 exceeds the
setting of the ROOM HOT item in the Monitor menu of RTU 1. The control will continue to operate
as normal with this warning. To clear the error message from the control, press either the Menu or
Item button.
This warning message will be displayed if the air temperature sensed by RTU 1 is below the
setting of the ROOM HOT item in the Monitor menu of RTU 1. The control will continue to operate
as normal with this warning. To clear the error message from the control, press either the Menu or
Item button.
Description of Error
31 of 32
© 2003
D 369e - 06/03