Kanmor Zone Control 369e Manual page 11

Table of Contents

Advertisement

ROOM TEMPERATURE UNIT (RTU) 063e
This RTU consists of one internal air sensor, three remote temperature sensor inputs,
a liquid crystal display (LCD) and four buttons. These buttons and the LCD are used
to set and view the desired room temperature, and for setback overrides. The RTU's
LCD displays the current room temperature, the outdoor air temperature, temperature
at the slab sensor, and a number of other items. In cases where a restricted tempera-
ture range is required, the RTU's range can be limited by changing the access level
of the RTU.
Remote indoor sensors can be connected to the 063e to average the air temperature reading. Typically, multiple remote sen-
sors are used in large open areas in a building to get an average indoor air temperature. Any type of 10K sensor can be con-
nected to the input(s) on the 063e.
Room or Slab Temperature Control using a Floor (Slab) Sensor
The RTU 063e can be configured for floor (slab) and air temperature control using a floor (slab) sensor connected to the Rs3
and Com terminals (3 & 5) and the air sensor in the RTU. The minimum and maximum floor (slab) temperature and air tem-
perature settings are adjusted at the RTU. The minimum and maximum slab setpoints have priority over the air temperature
setpoint. Once the slab setpoint(s) has been satisfied, the air temperature setpoint can then be satisfied.
If the air temperature sensor at the RTU is turned off, the air temperature is ignored.
REMOTE DISPLAY MODULE (RDM) 040e
This module provides the user with a remote interface to the 369e. The RDM can be
used to remotely monitor and adjust settings on the control and display RTUs. The
RDM can display any of the system and status indicators visible on the control and
display RTU. It also has a built in alarm contact that can be used to trigger an external
alarm if either a control or sensor error occurs, or if a limit has been reached.
To access the control's user interface, select CTRL through the DEVICE item in the
Misc menu. To access a display RTU's user interface, select RTUi (where i corre-
sponds to the appropriate zone) through the DEVICE item in the Misc menu.
© 2003
D 369e - 06/03
11 of 32