When installing the outdoor unit in a place that is constantly exposed to a
strong wind like a coast or on a high story of a building, secure a normal
fan operation by using a duct or a wind shield.
• Install the unit so that its discharge port faces to the wall of the
building.
Keep a distance 500mm(19-11/16inch) or more between the unit and
the wall surface.
• Supposing the wind direction during the operation season of the air
conditioner, install the unit so that the discharge port is set at right
angle to the wind direction.
500mm
(19-11/16inch)
Air inlet grille
Turn the air outlet side toward the
building's wall, fence or windbreak screen.
WARNING
!
Fix the outdoor unit firmly with anchor bolt or it may fall and hurt
people. (refer to 'Foundation for installation')
For Heat Recovery Installation
Select installation location of the HR unit suitable for following
conditions
- Avoid a place where rain may enter since the HR unit is for indoor.
- Sufficient service space must be obtained.
- Refrigerant pipe must not exceed limited length.
- Avoid a place subject to a strong radiation heat from other heat
source.
- Avoid a place where oil spattering, vapor spray or high frequency
electric noise is expected.
- Install the unit at a place in which it is not affected by operation noise.
(Installation within cell such as meeting room etc. may disturb
business due to noise.)
- Place where refrigerant piping, drain piping and electrical wiring
works are easy.
2 Series
481 (18-15/16)
7
1
2
3
Inspection door
(servicing space)
450 (17-23/32)
174
174
(6-27/32)
453 (17-27/32)
(6-27/32)
[Unit:mm(inch)]
More than 100 (3-15/16)
More than 100 (3-15/16)
More than 100 (3-15/16)
(Servicing space)
(Servicing space)
(Servicing space)
More than
More than
300 (11-13/16)
300 (11-13/16)
(Servicing space)
(Servicing space)
More than 100 (3-15/16)
More than 100 (3-15/16)
More than 100 (3-15/16)
(Servicing space)
(Servicing space)
(Servicing space)
More than
More than
300 (11-13/16)
450 (17-23/32)
(Servicing space)
(Servicing space)
124 (4-7/8)
4
5
419 (16-1/2)
137
61
6
(5-13/32)
(2-13/32)
3 Series
500(19-11/16)
7
Inspection door
(servicing space)
500(19-11/16)
150(5-29/32)
486(19-1/8)
150(5-29/32)
809(31-27/32)
7
Inspection door
(servicing space)
800(31-1/2)
2
3
1
160
160
(6-5/16)
793(31-7/32)
(6-5/16)
No.
Part Name
Low pressure Gas
Ø 28.58 (1-1/8)
1
pipe connection port
Brazing connection
High pressure Gas
Ø 22.2 (7/8) Brazing
2
pipe connection port
connection
Ø 15.88 (5/8) Brazing
connection
(PRHR042A)
Liquid pipe
3
connection port
Ø 12.7 (1/2) Brazing
connection
(PRHR032A)
Indoor unit Gas pipe
Ø 15.88 (5/8) Brazing
4
connection port
connection
Indoor unit Liquid
Ø 9.52 (3/8) Brazing
5
pipe connection port
connection
6 Control box
-
7 Hanger metal
M10 or M8
NOTE
!
• Be sure to install the inspection door at the control box side.
• If reducers are used, servicing space must be increased equal to
reducer's dimension.
6(1/4) more (Serviceing space)
300(11-13/16)
300(11-13/16)
(Servicing space)
(Servicing space)
6(1/4) more (Serviceing space)
300(11-13/16) more
254(10) more
(Servicing space)
(Servicing space)
126(4-31/32)
2
4
3
1
92
6
389(15-5/16)
176(6-15/16)
(3-5/8)
6(1/4) more (Serviceing space)
300(11-13/16) more
300(11-13/16) more
(Servicing space)
(Servicing space)
6(1/4) more (Serviceing space)
254(10) more
300(11-13/16) more
(Servicing space)
(Servicing space)
6
126(4-31/32)
4
92(3-5/8)
389(15-5/16)
176(6-15/16)
■ Unit: mm(inch)
Description
PRHR042A
PRHR032A
PRHR083A
PRHR022A
PRHR063A
PRHR023A
PRHR043A
PRHR033A
Ø 22.2 (7/8) Brazing
connection
Ø 19.05 (3/4) Brazing
connection
Ø 9.52 (3/8) Brazing
connection
Ø 15.88 (5/8) Brazing
connection
Ø 9.52 (3/8) Brazing
connection
-
M10 or M8
5
5