Flow chart of manual addressing for pipe de-
tection
Execute in case of Auto pipe detection
failure
Wait for about 5 minutes.
Turn No.1 of SW02M of HR unit PCB on.
The number of the indoor units installed is
displayed.
Reset the power of HR unit PCB.
Ex)HR
Enter the central control address into
each indoor unit using its wired remote
control.
of indoor units connected to the
outdoor unit and displayed one
On the HR unit PCB, manually set address
of each valve of the HR unit to the central
control address of the indoor unit
connected to the valve.
Completion of manual pipe detection
Reset the power of outdoor unit PCB.
Example of manual valve addressing (Non-
Zoning setting)
(In case that an indoor unit of central control address "11" is connected
to a valve #1 of an HR unit)
- Prerequisite for manual valve addressing: central control address of
each indoor unit must be preset differently at its wired remote con-
trol.
No.
Display and setup
- Operation: None
1
- Display: None
7-SEG
SW01M
SW03M
SW04M
- Operation: Turn dip S/W No.1 on to ad-
dress valve #1
2
- Display: Existing value saved in EEP-
7-SEG
SW01M
SW03M
SW04M
ROM is displayed in 7-SEG.
- Operation: Set the digit of 10 to the
number in Group High data of the wired
remote control connected to the corre-
sponding indoor unit to the valve #1 by
3
pressing left tack S/W.
7-SEG
SW01M
SW03M
SW04M
- Display: Digit increasing with the times
of pressing tack S/W is displayed in left
7-SEG
- Operation: Set the digit of 1 to the num-
ber in Group Low data of the wired re-
mote control connected to the
corresponding indoor unit to the valve
4
#1 by pressing right tack S/W.
7-SEG
SW01M
SW03M
SW04M
- Display: Digit increasing with the times
of pressing tack S/W is displayed in
right 7-SEG
- Operation: Turn dip S/W No.1 off to
save the address of valve #1
5
- Display: "11" displayed in 7-SEG disap-
7-SEG
SW01M
SW03M
SW04M
pears
- Above setup must be done for all HR unit valves.
- The valve that is not connected with any indoor unit should be ad-
dressed with any other number than used address numbers of the
valves connected with indoor units.
(The valves does not work if the address numbers are same.)
The number of the indoor
Are the number
NO
equal?
Check the central control address of
indoor and HR unit.
YES
Make sure that reset the outdoor
unit
power when changing the central
control unit
Setup and Contents
Example of manual valve addressing (Zoning
setting)
(In case that an indoor unit of central control address "11" is connected
to a valve #1 of an HR unit)
Zoning control is connecting 2 or more indoor units at one pipe of HR
unit. In case of Zoning control, in order to set controls with multiple in-
door units connection uses the rotary switch. Namely, only the rotary
switch changes from same valve set condition and set indoor units
connection.
1
On dip switch of the corresponding valves and sets the rotary
switch at 0.
2
Setting the number with tact switch.
3
In case of addition of indoor units to same port, increases 1 with the
rotary switch and sets number with tact switch.
4
In case of checking the number which the corresponding valve is
stored, turn on dip switch and set the number of rotary switch.
5
Indoor units set available 7 per a port(rotary switch 0~6), in case of
setting above of 7 with rotary switch, it will display error.
6
Setting the rotary switch on original condition(HR unit number set
conditions) after all finishing a piping setting.
7
The rotary switch set value of above number of indoor units which
is connected with FF and prevents a malfunction.
(Example: The case where 3 indoor units is connected in piping 1,
sets from rotary switch 0,1,2 and 3,4,5 with FF set)
- Prerequisite for manual valve addressing: central control address of
each indoor unit must be preset differently at its wired remote con-
trol.
No.
Display and setup
- Operation: None
0
1
- Display: None
7-SEG
SW01M
SW03M
SW04M
SW05M
- Operation : Turn dip S/W No.1 on to ad-
dress valve #1
0
2
- Display : Existing value saved in EEP-
7-SEG
SW01M
SW03M
SW04M SW05M
ROM is displayed in 7-SEG.
- Operation : Set the digit of 10(1) to the
number in Group High data of the wired
remote control connected to the corre-
sponding indoor unit to the valve #1 by
0
3
pressing left tack S/W.
7-SEG
SW01M
SW03M
SW04M SW05M
- Display : Digit increasing with the times
of pressing tack S/W is displayed in left
7-SEG.
- Operation : SW05M : 1
4
- Display : Display former value.
7-SEG
SW01M
SW03M
SW04M SW05M
- Operation : Setting No. using SW03M
and SW04M, SW05M : 1
5
- Display : Display setting value.
7-SEG
SW01M
SW03M
SW04M SW05M
- Operation : Turn dip S/W No.1 off to
save the address of valve #1
6
- Display : "11" displayed in 7-SEG disap-
7-SEG
SW01M
SW03M
SW04M SW05M
pears.
- Operation : Return valve of addressing
0
HR unit.
7
7-SEG
SW01M
SW03M
SW04M SW05M
- Display : None
- Above setup must be done for all HR unit valves.
- The valve that is not connected with any indoor unit should be ad-
dressed with any other number than used address numbers of the
valves connected with indoor units.
(The valves does not work if the address numbers are same.)
31