Automatic Addressing

The address of indoor units would be set by Automatic
Addressing
- Wait for 3 minutes after supplying power.
(Master and Slave outdoor units, indoor units)
- Press RED button of the outdoor units for 5 seconds. (SW01C)
- A "88" is indicated on 7-segment LED of the outdoor unit PCB.
- For completing addressing, 2~7 minutes are required depending on
numbers of connected indoor units
- Numbers of connected indoor units whose addressing is completed are
indicated for 30 seconds on 7-segment LED of the outdoor unit PCB
- After completing addressing, address of each indoor unit is indicated
on the wired remote control display window. (CH01, CH02,
CH03, ......, CH06 : Indicated as numbers of connected indoor units)
SERVICE PCB
7-Segment
SW01C(●:confirm)
SW02C(◀:backward)
SW03C(▶:forward)

The Procedure of Automatic Addressing

Power On
Waiting 3 minutes
Press RED Button for
5 seconds (SW01C)
Automatic addressing process start
7-segment LED
= 88
Don't press RED Button
(SW01C)
• Automatic addressing process end
Waiting about 2~7 minutes
Numbers of indoor unit connected are indicated for 30
seconds on 7-segment LED after completing process.
NO
7-segment LED
= 88
YES
Indoor address number is displayed on wired remote controller or
indoor unit display window. It is not an error message, will
disappeared when on/off button is pressed on remote controller
ex) Display of 01, 02, ..., 15 means connection of 15 indoor units
OK
and Automatic addressing is completed normally.
CAUTION
!
• In replacement of the indoor unit PCB, always perform Automatic
addressing setting again (At that time, please check about using
Independent power module to any indoor unit.)
• If power supply is not applied to the indoor unit, operation error
occur.
• Automatic Addressing has to be performed after more than 3
minutes to improve indoor unit communition when initial power is
supplied.
• Please be sure that all the DIP switch (1~7) of master outdoor unit is
OFF before Automatic Addressing setting
Setting For Heat Recovery Unit (Refer Only Heat Recovery Installation)
Automatic pipe detection
1
Turn No.1 of DIP s/w SW02E of HR unit PCB off.
2
Confirm that the setting of No.2, 3 of SW02E corresponds with the
type of the valve connection.
3
Reset the power of HR unit PCB
4
Master Out door unit PCB DIP switch on : No.5
5
Select the mode using '▶', '◀' Button : "Idu" Push the '●' button
6
Select the "Id 5" function using '▶', '◀' Button :"Atc" or ""Ath"
Push the '●' button.
Outdoor temperature is over 15 °C(59 °F) : "Ath" Using (If it fail, use
"Atc")
Outdoor temperature is below 15 °C(59 °F) : "Atc" Using (If it fail,
use "Ath")
7
Select the mode using '▶', '◀' Button : "Idu" Push the '●' button
8
Select the "Id 6" function using '▶', '◀' Button :"StA" Push the
'●' button
9
System is operated after "88" is displayed on 7 segment of the
outdoor unit main PCB.
10
Pipe detection process is proceeded.
11
5~30 minutes are required depending on the number of the indoor
units and outdoor temperature.
SW01D(reset)
12
The number of the indoor units connected is displayed on 7
SW04C(x:cancel)
segment of the outdoor unit main PCB for about 1 minute
- For a HR unit, the number of the indoor units connected to each
DIP-SWITCH
- '200' is displayed in case of auto pipe detecting error, and Auto
* Auto pipe detection function : the function that sets connection
!
• Execute auto addressing and auto pipe detection again whenever
• Error No.200 occurs if the number of connected indoor units and
• If auto pipe detection process fails, complete it with manual pipe
• If auto pipe detection process is completed normally, manual
• If you want to do auto pipe detection again after auto pipe
• During 5 minutes after pipe detection is completed, do not turn
Check the connections
of communication cable
Manual pipe detection
1
Enter the central control address into each indoor unit using its
wired remote controller.
2
Turn No.1 of DIP s/w SW02E of HR unit PCB on.
3
Reset the power of HR unit PCB.
4
On the HR unit PCB, manually set address of each valve of the HR
unit to the central control address of the indoor unit connected to
the valve.
5
Reset the power of outdoor unit PCB.
6
The number of the indoor unit installed is displayed after about 5
minutes.
Ex) HR ‡ The number of the indoor
7
Reset the power of outdoor unit PCB, HR unit.
8
Manual pipe detection is completed
HR unit is displayed.
pipe detection process is completed after '88' is disappeared.
relationship automatically between the indoor unit and HR unit.
WARNING
the indoor PCB and HR unit PCB is replaced.
- Operation error occurs unless power is supplied to the indoor
and HR units.
that of scanned indoor units are different.
detection (see Manual pipe detection part).
pipe detection is not required.
detection fails, do after reset of outdoor unit by all means.
off the main unit PCB to save the result of pipe detection
automatically.
41