34
Wiring of main power supply and equipment
capacity
- Use a separate power supply for the Outdoor Unit and Indoor Unit.
- Bear in mind ambient conditions (ambient temperature,direct
sunlight, rain water,etc.) when proceeding with the wiring and
connections.
- The cable size is the minimum value for metal conduit wiring. The
power cord size should be 1 rank thicker taking into account the line
voltage drops. Make sure the power-supply voltage does not drop
more than 10 %.
- Specific wiring requirements should adhere to the wiring regulations
of the region.
- Power supply cords of parts of appliances for outdoor use should not
be lighter than polychloroprene sheathed flexible cord.
- Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
WARNING
!
• Follow ordinance of your governmental organization for
technical standard related to electrical equipment, wiring
regulations and guidance of each electric power company.
• Make sure to use specified cables for connections so that no
external force is imparted to terminal connections. If
connections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection
switch. Note that generated overcurrent may include some
amount of direct current.
CAUTION
!
• All installation site must require attachment of an earth leakage
breaker. If no earth leakage breaker is installed, it may cause an
electric shock.
• Do not use anything other than breaker and fuse with correct
capacity. Using fuse and wire or copper wire with too large capacity
may cause a malfunction of unit or fire.

Field Wiring

Single outdoor unit
Power supply switch
(Switch fuse : ELCB)
Power supply
1 Phase
208/230V, 60Hz
(Main Switch)
Power supply switch
(Switch fuse)
Power supply
1 Phase
208/230V, 60Hz
HR unit
HR unit
WARNING
!
• Indoor unit ground lines are required for preventing electrical shock
accident during current leakage, Communication disorder by noise
effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect
each of indoor unit separately from the power supply.
• Install the main switch that can interrupt all the power sources in an
integrated manner because this system consists of the equipment
utilizing the multiple power sources.
• If there exists the possibility of reversed phase, lose phase,
momentary blackout or the power goes on and off while the
product is operating, attach a reversed phase protection circuit
locally. Running the product in reversed phase may break the
compressor and other parts.
• When using shielded wires, perform a single-point grounding only
to the outdoor unit for grounding of communication wires.
Example) Connection of transmission wire
[BUS type]
- Connection of communication
cable must be installed like
below figure between indoor
unit to outdoor unit.
HR unit
: Single phase of power supply line[L1(L),L2(N)]
: Communication line (3 line): Wired remote control
: Communication line (2 shield line):
Between Indoor Unit and Outdoor Unit
Pull Box(Installer Option)
[STAR type]
- Abnormal operation can be
caused by communication
defect, when connection of
communication cable is installed
like below figure(STAR type).
HR unit