Model 6-Wire; Model 12-Wire - Fluke Thermalert 4.0 Series User Manual

Smart integrated infrared sensors
Table of Contents

Advertisement

2.3.4 Model 6-Wire

Power
Outputs
Analog
Digital
The 6-wire version is not available for LTB-30 models.

2.3.5 Model 12-Wire

Power
Outputs
Analog
Alarm
Input
Analog
Digital
Digital
The 12-wire version is not available for LTB-30 models.
1.800.561.8187
+ 24 VDC nominal (20 to 48 VDC), 100 mA @ 24 V
0 to 20 mA (active), or
4 to 20 mA (active), or
0 to 10 V, or
J thermocouple, or
K thermocouple
current loop impedance: max. 500 Ω
voltage load impedance: min. 10 kΩ
electrically isolated from power supply
USB: version 2.0, micro-B connector (only for the setup of the instrument)
RS485: networkable to 32 sensors,
baud rate: 4800, 9600, 19200, 38400, 57600, 115200 Bit/s (default: 9600 Bit/s)
+ 24 VDC nominal (20 to 48 VDC), 100 mA @ 24 V
0 to 20 mA (active), or
4 to 20 mA (active), or
0 to 10 V
current loop impedance: max. 500 Ω
voltage load impedance: min. 10 kΩ
electrically isolated from power supply
48 V / 300 mA
1 potential-free relay output with wear-free contacts (solid state relay),
electrically isolated from power supply
0 to 10 V
emissivity setting, or
background temperature compensation
trigger input (closing contact)
USB: version 2.0, micro-B connector (only for the setup of the instrument)
RS485: networkable to 32 sensors,
baud rate: 4800, 9600, 19200, 38400, 57600, 115200 Bit/s (default: 9600 Bit/s)
www.
.com
Technical Data