Operation instructions of wire controller
Name
Restore the default value
Selection for cooling control
Selection for heating control
Selection for brine chiller
Temperature control period
Action return difference of chilled
water
Action return difference of cooling
water
Action return difference of
hot-water
Number of combined modules
BAS Modbus address
Compensation for system's chilled
backwater sensor
Compensation for system's chilled
outflow-water sensor
Compensation for system's
cooling backwater sensor
Compensation for system's
cooling outflow-water sensor
Adjustable multiplying power
Power-on heating water return
difference
Power-off heating water return
difference
Alarm for excessively low chilled
outflow-water temperature
Alarm for excessively low chilled
outflow water temperature - saline
water
Alarm for excessively high
cooling outflow-water temperature
Limit value for excessively low
suction pressure
Limit value for excessively low
suction pressure - saline water
Maximum limit value for exhaust
pressure
Email: sales@cookeindustries.co.nz
Set range
0~1
1-Reset
0 - backwater
constant-water-temperature
0~1
control; 1 - outflow-water
constant-water-temperature
control
0 - backwater
constant-water-temperature
0~1
control; 1 - outflow-water
constant-water-temperature
control
Un-settable
0-standard; 1-brine chiller
Un-settable
Seconds
1.0~3.0
°C
1.0~3.0
°C
5.0~20.0
°C
1~8
1~255
Un-settable
°C
Un-settable
°C
Un-settable
°C
Un-settable
°C
Un-settable
0, 1, 2, 3, 4, 5, 6
0.0~10.0
°C
0.0~5.0
°C
Un-settable
°C
Un-settable
°C
Un-settable
°C
Un-settable
kPa
Un-settable
kPa
Un-settable
kPa
42