Operating Range - York 21RT-47RT Installation, Operation And Maintenance Manual

Water-cooled chiller
Table of Contents

Advertisement

1.4. Operating Range

Voltage Range
Standard of Power Supply: 380VAC -3N-50Hz
Maximum allowable fluctuation range of the power supply voltage shall be ±10%
Unbalance rate of the three-phase voltage shall be less than 2%
Temperature Range
Usage environment for 7-inch screen controller
Usage environment for wire controller
Temperature range of unit's operating environment
Operation of Cooling
Operation of Heating
Operation of Heat Recovery
Note:
 Returning water temperature control is set as default and recommended
 The above data is obtained in the laboratory. In actual use, it will be biased by the influence factors, such as
installation location, etc.
 * Saline-water Mode (for ethylene glycol aqueous solution only), and the set value shall be selected in
accordance with ethylene glycol's concentration
 Water temperature's operating range diagram for standard unit is as follows
Note: The above diagram is standard unit operating range diagram. For the operation range of saline-water mode,
please consult Johnson Controls
Other Requirements:
Cooke Industries - Phone: +64 9 579 2185
/ 400VAC-3N-50Hz
Items
Email: sales@cookeindustries.co.nz
Range
-20 - 60°C; RH≤95%; Noncondensing
0-50°C, RH-95%; Noncondensing
-10°C -48°C
Using-side water inflow 10°C (-5°C*) - 30°C
Using-side water outflow 5°C (-10°C*) - 24°C
Heat-source-side water inflow 15°C - 50°C
Using-side water inflow 15°C - 50°C
Using-side water outflow 20°C - 55°C
Heat-source-side water inflow 10°C - 30°C
Using-side water inflow 10°C - 30°C
Using-side water outflow 5°C - 24°C
Returning hot water 30°C - 50°C
7
Introduction of Unit