AIR-COOLED SCROLL CHILLER Supersedes: 150.72-ICOM6 (817) Form 150.72-ICOM6 (1217) INSTALLATION, OPERATION, MAINTENANCE 035-23572-100 YLAA0058 - YLAA0230 AIR-COOLED SCROLL CHILLERS WITH BRAZED PLATE HEAT EXCHANGER STYLE B (60 HZ) 4-10 FAN 55 - 230 TON 195 - 700 KW R-410A Issue Date: Products are produced at a December 29, 2017 f a c i l i t y w h o s e q u a l i t y -...
Page 2
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or During rigging, installation, operation, maintenance, death to themselves and people at the site. or service, individuals may be exposed to certain com- This document is intended for use by owner-authorized ponents or conditions including, but not limited to:...
Page 3
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls’ policy for con- regarding the applicability of these documents, rig- tinuous product improvement, the information con- ging, lifting, and operating/service personnel should tained in this document is subject to change without verify whether the equipment has been modified and notice.
Page 4
17 = 200-3-60 28 = 230-3-60 40 = 380-3-60 46 = 460-3-60 58 = 575-3-60 S = STANDARD EFFICIENCY H = HIGH EFFICIENCY FOUR DIGIT UNIT NUMBER A = DESIGN SERIES A = AIR COOLED YL = YORK CHILLER JOHNSON CONTROLS...
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 TABLE OF CONTENTS SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETY ..............11 Introduction ..............................11 Warranty ................................. 11 Handling ................................. 11 Safety and Quality ............................11 About this Manual ............................12 Misuse of Equipment ............................12 SECTION 2 –...
Page 6
Return Chilled Liquid System Lead/Lag and Compressor Sequencing ............153 Anti-Recycle Timer ............................153 Anti-Coincidence Timer ..........................153 Evaporator Pump Control and York Hydro Kit Pump Control ............... 153 Evaporator Heater Control ........................... 154 Pumpdown Control ............................154 Standard Condenser Fan Control ........................ 154 Load Limiting ..............................
Page 7
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 TABLE OF CONTENTS (CONT’D) SECTION 9 – SERVICE AND TROUBLESHOOTING ..................161 Clearing History Buffers..........................161 Service Mode ............................... 161 Service Mode – Outputs ..........................161 Service Mode – Chiller Configuration ......................162 Service Mode – Analog and Digital Inputs ....................162 Control Inputs/Outputs ..........................
Page 8
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 LIST OF FIGURES FIGURE 1 - Unit Components (Front) ........................20 FIGURE 2 - Unit Components (Side) ........................21 FIGURE 3 - Power Panel Components ........................22 FIGURE 4 - Power Panel / Control Components ....................23 FIGURE 5 - Process and Instrumentation Diagram ....................29 FIGURE 6 - Unit Rigging/Lifting ..........................32 FIGURE 7 - Warning ...............................34 FIGURE 8 - Chilled Liquid System .........................37...
Page 9
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 LIST OF TABLES TABLE 1 - Canadian Registration Numbers ......................16 TABLE 2 - Complete Pin Number Description ......................24 TABLE 3 - Temperatures and Flows ........................43 TABLE 4 - Ethylene and Propylene Glycol Correction Factors ................45 TABLE 5 - Physical Data (English) 60 Hz .......................46 TABLE 6 - Micropanel Power Supply ........................48 TABLE 7 - Voltage Range ............................48...
Page 10
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETY INTRODUCTION YORK YLAA chillers are manufactured to the highest serial number information is printed on the unit identi- design and construction standards to ensure high per- fication plate.
FORM 150.72-ICOM6 SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETY ISSUE DATE: 12/29/2017 • ASHRAE 90.1 - Energy Efficiency compliance. Structural Support Structural support of the unit must be provided as in- • Conform to Intertek Testing Services, formerly dicated in these instructions. Failure to provide proper ETL, for construction of chillers and provide support may result in injury to the operator, or damage ETL/cETL listing label.
Page 13
FORM 150.72-ICOM6 SECTION 1 – GENERAL CHILLER INFORMATION AND SAFETY ISSUE DATE: 12/29/2017 Rotating Parts High Temperature and Pressure Cleaning Fan guards must be fitted at all times and not removed High temperature and pressure cleaning methods unless the power supply has been isolated. If ductwork (e.g.
Page 14
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
ISSUE DATE: 12/29/2017 SECTION 2 – PRODUCT DESCRIPTION INTRODUCTION GENERAL SYSTEM DESCRIPTION YORK YLAA Air-Cooled Scroll Chillers provide Compressors chilled water for all air conditioning applications us- The chiller has suction-gas cooled, hermetic, scroll ing central station air handling or terminal units. They compressors.
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 12/29/2017 The evaporator is equipped with a thermostat-con- vibration free operation. They are directly driven by trolled heater. The heater provides freeze protection independent motors, and positioned for vertical air dis- for the evaporator down to -20°F (-29°C) ambient.
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 12/29/2017 • Number of compressors • Liquid solenoid valve status • Low liquid temperature cutout • Load and unload timer status • Low suction pressure cutout • Water pump status • High discharge pressure cutout Provisions are included for: pumpdown at shutdown;...
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 12/29/2017 ACCESSORIES AND OPTIONS High Ambient Kit With Sunshield Allows units to operate when the ambient temperature Power Options is above 115°F (46°C). Includes sun shield panels and Compressor Power Connections discharge pressure transducers.
Page 19
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 12/29/2017 and is easily attached to the evaporator at startup us- exceed five miles per hour. The following types of en- ing the supplied ANSI/AWWA C-606 connector. The closure panels are available: flow switch can be deleted if alternate or existing flow •...
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 12/29/2017 POWER POWER PANEL PANEL ITEM DESCRIPTION Fan Assemblies MCHX Condenser Control Panel Compressors Receiver Included with Optional Heat Recovery Condenser Filter Driers FIGURE 1 - UNIT COMPONENTS (FRONT) JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 12/29/2017 ITEM DESCRIPTION Fan Deck MCHX Condenser Coil Headers Control and Power Panels Compressors Brazed Plate Evaporator Formed Steel Base Rails Hydro-Kit Pumps And Motors (Optional) FIGURE 2 - UNIT COMPONENTS (SIDE) JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 12/29/2017 LD13248 ITEM DESCRIPTION Fan Contactor Fan Fuses Control Relay Microcomputer Control Center Display Keypad XTBC1 Microboard XTCB2 XTBF2 Compressor Contactors Compressor Overloads FIGURE 4 - POWER PANEL / CONTROL COMPONENTS JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 12/29/2017 PRODUCT IDENTIFICATION NUMBER (PIN) TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION FEATURE FEATURE OPTION OPTION DESCRIPTION DESCRIPTION MODEL Model (PIN 1-4) YLAA 0058 0058 0065 0065 0070 0070 0080 0080 0081 0081 0089...
Page 25
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 12/29/2017 TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION (CONT’D) FEATURE FEATURE OPTION OPTION DESCRIPTION DESCRIPTION No Power Capacitor required Power Factor Capacitor Power Capacitor required (PIN 19) Special Power Capacitor required High Ambient Kit Standard (factory) Both Low/High Ambient Kit required (factory) Ambient Kits...
Page 26
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 12/29/2017 TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION (CONT’D) FEATURE FEATURE OPTION OPTION DESCRIPTION DESCRIPTION OVERLOAD PIN 35 Special Quote Quick Start PIN36 PIN 36 Special Quote Crankcase Heater Crankcase Heater Standard Special Crankcase Heater required (Pin 37) 150psig DWP Waterside...
Page 27
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 12/29/2017 TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION (CONT’D) FEATURE FEATURE OPTION OPTION DESCRIPTION DESCRIPTION No Acoustic Blanket required Acoustic Blanket Acoustic Blanket Required ACOUSTIC Acoustic Enclosure (PIN 49) Special Acoustic Blanket required No Documents Required Base, Material &...
Page 28
FORM 150.72-ICOM6 SECTION 2 – PRODUCT DESCRIPTION ISSUE DATE: 12/29/2017 TABLE 2 - COMPLETE PIN NUMBER DESCRIPTION (CONT’D) FEATURE FEATURE OPTION OPTION DESCRIPTION DESCRIPTION PIN 58 PIN 58 Marketing Purposes Only! No Pump Pump Kit A Pump Kit B Pump Kit C Pump Kit D Pump Kit E Pump Kit F...
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 SECTION 3 – HANDLING AND STORAGE DELIVERY AND STORAGE INSPECTION To ensure consistent quality and maximum reliability, Remove any transit packing and inspect the unit to en- all units are tested and inspected before leaving the fac- sure that all components have been delivered and that tory.
FORM 150.72-ICOM6 SECTION 3 – HANDLING AND STORAGE ISSUE DATE: 12/29/2017 LD18120 4 Fan Units LD18121 5 - 12 Fan Units FIGURE 6 - UNIT RIGGING/LIFTING JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 3 – HANDLING AND STORAGE ISSUE DATE: 12/29/2017 LIFTING USING LUGS LIFTING USING SHACKLES Units are provided with lifting holes in the base frame The shackles should be inserted into the respective which accept the accessory lifting lug set as shown in holes in the base frame and secured from the inside.
FORM 150.72-ICOM6 SECTION 3 – HANDLING AND STORAGE ISSUE DATE: 12/29/2017 LD18119 FIGURE 7 - WARNING Rigging and lifting should only be done by LIFTING WEIGHTS a professional rigger in accordance with a See the unit nameplate for unit shipping weight. Note written rigging and lifting plan.
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 SECTION 4 – INSTALLATION To ensure warranty coverage, this equip- In installations where winter operation is intended and ment must be commissioned and serviced snow accumulations are expected, additional height by an authorized Johnson Controls must be provided to ensure normal condenser air flow.
Hand stop valves should be installed in all lines to fa- cilitate servicing. 7. A chilled water flow switch, (either by YORK or others) MUST be installed in the leaving water pip- Piping to the inlet and outlet connections of the chiller ing of the cooler.
FORM 150.72-ICOM6 SECTION 4 – INSTALLATION ISSUE DATE: 12/29/2017 PIPEWORK ARRANGEMENT When ducting is to be fitted to the fan discharge it is recommended that the duct should be the same cross- The following are suggested pipework arrangements sectional area as the fan outlet and straight for at least for single unit installations, for multiple unit installa- three feet (1 meter) to obtain static regain from the fan.
FORM 150.72-ICOM6 SECTION 4 – INSTALLATION ISSUE DATE: 12/29/2017 aluminum to copper. This transition should be done in Alarm Status Contacts an external box separate to the power panel. Copper Normally-open contacts are available for each re- conductors can then be run from the box to the chiller. frigerant system.
FORM 150.72-ICOM6 SECTION 4 – INSTALLATION ISSUE DATE: 12/29/2017 Thermal Dispersion Flow Switch: 1. Thermal Dispersion Flow Switch Operating Principle PIN NUMBERS The operating principle of the thermal dispersion flow switch is based on the calorimetric princi- ple. It uses the cooling effect of a flowing fluid to monitor the flow rate.
FORM 150.72-ICOM6 SECTION 4 – INSTALLATION ISSUE DATE: 12/29/2017 USER CONTROL WIRING OUTPUTS INTERNAL WIRING TO EVAPORATOR HEATER INTERNAL WIRING TO HOT GAS SOLENOID VALVE SYSTEM 2 ALARM DRY CONTACTS (OPEN = ALARM) SYSTEM 1 ALARM DRY CONTACTS (OPEN = ALARM) SYSTEM 2 RUN DRY CONTACTS (CLOSE = RUN) SYSTEM 1 RUN DRY CONTACTS (CLOSE = RUN) EVAPORATOR PUMP DRY CONTACTS (CLOSE = RUN...
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 SECTION 5 – TECHNICAL DATA OPERATIONAL LIMITATIONS (ENGLISH) TABLE 3 - TEMPERATURES AND FLOWS TEMPERATURE AIR ON CONDENSER (°F) UNIT WATER FLOW WATER FLOW DESIGNATION (GPM) MIN (GPM) MAX STANDARD EFFICIENCY YLAA0070SE YLAA0080SE YLAA0089SE YLAA0100SE YLAA0120SE YLAA0136SE YLAA0155SE...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 ELECTRICAL DATA TABLE 6 - MICROPANEL POWER SUPPLY OVER CURRENT PROTECTION, CONTROL UNIT VOLTAGE SEE NOTE B NF DISC SW POWER NOTE A UNIT MODELS W/O VOLTAGE 115-1-60/50 CONTROL 30 A / 240V TRANS 200-1-60 30 A / 240V...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 TABLE 10 - ELECTRICAL DATA WITHOUT PUMPS MIN DUAL MAX DUAL CHILLER VOLTAGE MIN CKT. MIN N/F ELEM ELEM MODEL CODE AMPS DISC SW FUSE & FUSE MIN CB MAX CB JOHNSON CONTROLS...
Page 51
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 TABLE 10 - ELECTRICAL DATA WITHOUT PUMPS (CONT’D) SYSTEM # 1 SYSTEM # 2 COMPR 1 COMPR 2 COMPR 3 STD FLOW FANS COMPR 1 COMPR 2 COMPR 3 STD FLOW FANS LRA QTY LRA QTY 57.7...
Page 52
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 TABLE 10 - ELECTRICAL DATA WITHOUT PUMPS (CONT’D) MIN DUAL MAX DUAL CHILLER VOLTAGE MIN CKT. MIN N/F ELEM ELEM MODEL CODE AMPS DISC SW FUSE & FUSE MIN CB MAX CB 1000 1000...
Page 53
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 TABLE 10 - ELECTRICAL DATA WITHOUT PUMPS (CONT’D) SYSTEM # 1 SYSTEM # 2 COMPR 1 COMPR 2 COMPR 3 STD FLOW FANS COMPR 1 COMPR 2 COMPR 3 STD FLOW FANS LRA QTY LRA QTY 106.2 523 106.2 523...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 ELECTRICAL NOTES the rated load amps for all other loads included in NOTES 1. Minimum Circuit Ampacity (MCA) is based on the circuit. Otherwise, HACR-type circuit breakers 125% of the rated load amps for the largest mo- must be used.
Page 57
HEATER RELAY STANDARD YORK ACCESSORIES COMPRESSOR CONTACTOR - KM WIRING AND ITEMS SHOWN THUS ARE (INCLUDING COIL SUPPRESSOR) NOT SUPPLIED BY YORK - KCR CONTROL RELAY ITEMS THUS ENCLOSED FORM A COMPO- PUMP CONTACTOR PART NENTS OR SETS OF COMPONENTS...
Page 58
Thus, these circuits when used must be fed via the common point of isolation the voltage to these circuits is removed when the common point of isolation to the unit is opened. This common point of isolation is not supplied by YORK.
Page 59
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 ELECTRICAL NOTES AND LEGEND (CONT’D) Field installed on remote evaporator units. Fitted on units with single phase motors only. Fitted on units with low ambient option only. Only fitted on units with an acoustic kit. Only fitted on heat recovery units.
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 WIRING DIAGRAMS ELEMENTARY WIRING DIAGRAMS 035-21583-101 REV O 1/2.1 What these numbers mean. Example: 1 = follow wire no.1 2. = is the DWG number on the bottom center of each page. .1 = is the locator number across the top of the page.
Page 61
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 DWG. 1 FIGURE 14 - ELEMENTARY WIRING DIAGRAM (CONT’D) JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 035-21583-102 REV O DWG. 2 1/2.1 What these numbers mean. Example: 1 = follow wire no.1 2. = is the DWG number on the bottom center of each page. .1 = is the locator number across the top of the page. At the top of the pages the numbers 1 to 11 go from left to right.
Page 63
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 LD16751b DWG. 2 FIGURE 15 - ELEMENTARY WIRING DIAGRAM (CONT’D) JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 FAN WIRING 035-21583-125 REV - A 1L1/1.1 1L2/1.1 1L3/1.1 =1-F4 NB21 NB15 NB27 =1-F5 X/2.8 -AMB 2/1.2 LD21181a FIGURE 16 - FAN WIRING, STANDARD AIR FLOW JOHNSON CONTROLS...
Page 65
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 2L1/1.5 2L2/1.5 2L3/1.5 =2-F4 NB27 =2-F5 Y/2.8 LD21181b FIGURE 16 - FAN WIRING, STANDARD AIR FLOW (CONT’D) JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 FAN WIRING 035-21583-118 REV F LD21180a FIGURE 17 - FAN WIRING, HIGH AIR FLOW JOHNSON CONTROLS...
Page 67
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 LD21180b FIGURE 17 - FAN WIRING, HIGH AIR FLOW (CONT’D) JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 SINGLE AND DUAL POINT WIRING OPTIONS 035-21583-116 REV C SINGLE POINT WIRING OPTIONS DUAL POINT WIRING OPTIONS DWG. 16 LD21208 FIGURE 18 - SINGLE AND DUAL POINT WIRING OPTIONS JOHNSON CONTROLS...
Page 69
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 FOUR FAN UNITS DIMENSIONS – YLAA0058HE, YLAA0065HE, YLAA0081HE LD18072 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance.
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 FOUR FAN UNITS DIMENSIONS – YLAA0070SE, YLAA0080SE, YLAA0089SE LD18073 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance.
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 FIVE FAN UNITS DIMENSIONS – YLAA0100SE LD18074 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance.
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 SIX FAN UNITS DIMENSIONS – YLAA0120SE, YLAA0092HE, YLAA0101HE LD18075 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance.
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 EIGHT FAN UNITS DIMENSIONS – YLAA0136SE, YLAA0155SE, YLAA0142HE LD18076 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance.
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 TEN FAN UNITS DIMENSIONS – YLAA0170SE, YLAA0156HE, YLAA0175HE LD18077 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance.
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 TWELVE FAN UNITS DIMENSIONS – YLAA0200HE, YLAA0230HE LD21039 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable operation, and ease of maintenance.
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 WEIGHT DISTRIBUTION AND ISOLATOR Whenever the isolator option is ordered, the isolators MOUNTING POSITIONS will be shipped loose with the chiller. Packed with the isolators and also in the control panel informa- General tion packet is a drawing and table specifically for each Weights of specific chiller models vary significantly as...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 CLEARANCES See Figure 32 below for minimum clearances for all YLAA units. (2 m) (1.3 m) NOTES: 1. No obstructions allowed above the unit. 2. Only one adjacent wall may be higher than the unit. 3.
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 ISOLATOR LOCATIONS FOUR FAN ISOLATOR LOCATIONS YLAA0058HE, YLAA0065HE, YLAA0081HE LD18078 FOUR FAN ISOLATOR LOCATIONS YLAA0070SE, YLAA0080SE, YLAA0089SE LD18079 All dimensions are inches unless otherwise specified. JOHNSON CONTROLS...
Page 90
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 FIVE and SIX FAN ISOLATOR LOCATIONS YLAA0100SE, YLAA0120SE, YLAA0092HE, YLAA0101HE LD18080 EIGHT FAN ISOLATOR LOCATIONS YLAA0136SE, YLAA0155SE, YLAA0142HE LD18081 All dimensions are inches unless otherwise specified. JOHNSON CONTROLS...
Page 91
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 TEN FAN ISOLATOR LOCATIONS YLAA0170SE, YLAA0156HE, YLAA0175HE LD18082 TWELVE FAN ISOLATOR LOCATIONS YLAA0200HE, YLAA0230HE VIEW LD21040 All dimensions are inches unless otherwise specified. JOHNSON CONTROLS...
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 ISOLATOR INFORMATION One Inch Deflection Spring Isolator Cross-reference 5/8" Ø1/2" H" C" T" B" L" D" W" LD13759A MOUNT DIMENSION DATA (INCHES) TYPE 7-3/4 6-1/2 4-3/4 5-5/8 10-1/2 9-1/4 7-3/4 9/16 MODEL NUMBER RATED CAPACITY (LBS)
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 ONE INCH DEFLECTION SPRING ISOLATORS INSTALLATION INSTRUCTIONS 1. Read instructions in their entirety before begin- 6. The adjustment process can only begin after the ning installation. equipment or machine is at its full operating weight.
Page 95
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 2” DEFLECTION ISOLATOR INSTALLATION AND ADJUSTMENT 1. Read instructions in their entirety before begin- equipment or bracket to the top plate (“A”) of iso- ning installation. lator with a minimum of 3/8 fillet welds 2" long @ 3"...
Page 96
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 NEOPRENE ISOLATOR CROSS-REFERENCE RD-Style Isolators MOLDED DURULENE ø D THRU TYP 2 PLACES LD13760A 1. All dimensions are inches, interpreted per ANSI 4. AL = Mounting hole center to center spacing. Y14.
Page 97
FORM 150.72-ICOM6 SECTION 5 – TECHNICAL DATA ISSUE DATE: 12/29/2017 INSTALLATION OF NEOPRENE VIBRATION ISOLATORS 1. Read instructions in their entirety before begin- 4. Bolt or anchor all isolators to supporting structure ning installation. utilizing base thru holes (“B”). 2. Isolators are shipped fully assembled and are to be 5.
Page 98
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 SECTION 6 – COMMISSIONING Commissioning of this unit should only Charging after vacuuming - NEVER add be carried out by Johnson Controls Au- more than 5% of specified amount into the thorized personnel. evaporator. This will lead to compressor failure when compressor starts.
Page 100
Supply Voltage of clean hose or copper line, but do not tighten the flare nut. Use YORK “V” oil 011-00949-000, when adding Verify that the site voltage supply corresponds to the oil to Copeland compressor. The Bitzer compressor unit requirement and is within the limits given in SEC- uses 011-00982-000 oil.
FORM 150.72-ICOM6 SECTION 6 – COMMISSIONING ISSUE DATE: 12/29/2017 The machine is now live! Flow Switch Verify a chilled water flow switch is correctly fitted in the customer’s piping on the cooler outlet, and wired into the control panel correctly using shielded cable. There should be a straight run of at least 5 pipe diam- eters on either side of the flow switch.
FORM 150.72-ICOM6 SECTION 6 – COMMISSIONING ISSUE DATE: 12/29/2017 HOW TO COMMISSION THE PUMP VFD 1. Put pump in HAND mode. LD18421 LD18422 6. Set parameter 22-89 to the Sensorless Flow read- out taken in the previous step. LD18418 2. Change parameter 0-20 (default value is option 1601 –...
Page 103
FORM 150.72-ICOM6 SECTION 6 – COMMISSIONING ISSUE DATE: 12/29/2017 Supersedes: 150.72-CL1 (817) Form 150.72-CL1 (1217) MODEL - YLAA STARTUP CHECKLIST CUSTOMER: ____________________________________ JOB NAME: ____________________________________ ADDRESS: _____________________________________ LOCATION: ____________________________________ PHONE: ________________________________________ CUSTOMER ORDER NO: _________________________ JCI TEL NO: _____________________ JCI ORDER NO: __________________ JCI CONTRACT NO: ______________ CHILLER MODEL NO: ____________________________ UNIT SERIAL NO: _______________________________...
Page 104
Remote Temperature Reset External Evaporator Pump 7. Place the Unit Switch in the control panel to the ON position............... YORK Hydro Kit Pump NOTE: The chilled liquid setpoint may need to Pump Selection be temporarily lowered to ensure all compres- Data Log to Flashcard sors cycle ON.
Page 105
FORM 150.72-ICOM6 SECTION 6 – COMMISSIONING ISSUE DATE: 12/29/2017 FORM 150.72-CL1 ISSUE DATE: 12/29/2017 D. CHECKING SUPERHEAT AND SUBCOOLING 12. Record the suction temperature, suction pressure, saturation temperature, and superheat of each sys- The subcooling temperature of each system can be calcu- tem below: ..............
Page 106
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
LD13283 INTRODUCTION IPU II AND I/O BOARDS The YORK Control Center is a microprocessor based The IPU and I/O boards are assembled to function as control system designed to provide the entire control a single microprocessor controller. The IPU II board for the liquid chiller.
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 plied power for the micro board +5V supply. 24VAC KEYPAD is rectified, but not regulated, to provide unregulated The 12 button non-tactile keypad allows the user to +30VDC to supply all of the digital inputs. retrieve vitals system parameters such as system pres- sures, temperatures, compressor running times and The I/O board contains one green “Power”...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 STATUS KEY 00066VIP Unit Status D A I L Y S C H E D U L E Pressing the STATUS key will enable the operator to S H U T D O W N determine current chiller operating status.
Page 110
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 The limiting pressure is a factory set limit to keep the S Y S C O O L L O A D system from faulting on the high discharge pressure S Y S C O O L L O A D...
Page 111
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 OVERRIDE is to only be used in emergencies or for S Y S L O W S U C T P R E S S servicing. Manual override mode automatically disables S Y S L O W S U C T...
Page 112
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 The internal motor protector opens at 185 °F to 248 °F This safety will shut down a system if either suction (85 °C to 120 °C) and auto resets. The mechanical HP temperature or suction pressure sensors read out of switch opens at 585 PSIG plus or minus 10 PSIG (27.92 range high or low.
Page 113
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 setpoints, program values, options, time, schedule, and U N I T F A U L T : history buffers will be lost. These values will all be re- H I G H M T R C U R R set to their default values which may not be the desired...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 STATUS KEY MESSAGES General Messages Fault Messages Unit Safeties & System Safeties Unit Switch Off Warning Messages Shutdown Remote Controlled System X High Disch Pressure Low Ambient Temp Shutdown Daily Schedule Low Liquid Temp System X Low Suct Pressure Shutdown...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 DISPLAY/PRINT KEYS 00067VIP The Display/Print keys allow the user to retrieve sys- With the “UNIT TYPE” set as a liquid chiller (no tem and unit information that is useful for monitoring jumper from J11-7 to J11-12 on the I/O Board), the chiller operation, diagnosing potential problems, trou- following list of operating data screens are viewable...
Page 116
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 S Y S 7 2 . 1 P S I G C O O L I N G D E M A N D = 2 2 7 . 0 P S I G S T E P S These displays show suction and discharge pressures...
Page 117
2 message is displayed. ISN – YORK Talk via ISN allows remote load limiting and temperature reset through an ISN system. The fourth message indicates the stage of condenser fan operation that is active.
DEFROST TERMINATION TIME 3MIN BIVALENT HEAT DELAY TIME 30 MIN Current Feedback One Per System REMOTE UNIT ID PROGRAMMED YORK HYDRO KIT PUMPS 1 (410a) PUMP TOTAL RUN HOURS XXXXX (410a) * Block of information repeats for each system LD12585 UNIT DATA RETURN LIQUID TEMP 58.2 DEGF...
Page 119
MON START=00:00AM STOP=00:00AM TUE START=00:00AM STOP=00:00AM follows. WED START=00:00AM STOP=00:00AM THU START=00:00AM STOP=00:00AM FRI START=00:00AM STOP=00:00AM YORK INTERNATIONAL CORPORATION SAT START=00:00AM STOP=00:00AM MILLENNIUM LIQUID CHILLER HOL START=00:00AM STOP=00:00AM SAFETY SHUTDOWN NUMBER 1 SHUTDOWN @ 3:56PM 29 SEP 07...
Page 120
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 History Displays C O N T R O L M O D E The HISTORY key gives the user access to many unit L E A V I N G L I Q U I D and system operating parameters at the time of a unit or system safety shutdown.
Page 121
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 L E A D S Y S T E M L E A V I N G L I Q U I D T E M P S Y S T E M N U M B E R C U T O U T X X X .
Page 122
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 der the PROGRAM key, the display will be the first S Y S S U C T X X X . X ° F display prior to the SYS 1 info. If the microprocessor is S A T S U C T X X X .
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 ENTRY KEYS 00068VIP The Entry Keys allows the user to view, change pro- Enter/Adv Key grammed values. The ENTRY keys consist of an ↑ (UP) The ENTER/ADV key must be pushed after any change arrow key, ↓...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 SETPOINTS KEYS 00069VIP Programming of the cooling setpoints, daily schedule, Leaving Chilled Liquid Control and safeties is accomplished by using the keys located S E T P O I N T 4 5 .
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 the control range. If the control mode has been pro- The following messages illustrate both leaving chilled grammed for RETURN LIQUID control, the message liquid control and return chilled liquid control respec- below would be displayed in place of the previous tively.
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 PROGRAM KEY L O W A M B I E N T T E M P C U T O U T 2 5 . 0 ° F There are several operating parameters under the PRO- GRAM key that are programmable.
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 This MUST be programmed correctly to F A N D I F F E R E N T I A L O F F assure proper chiller operation. P R E S S U R E X X X P S I G The Fan Differential Off Pressure is the programmed...
Page 129
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 Depending on the option, the trip voltage for a Unit Trip Volts specific system or unit high current trip can be For total chiller high current trip programming on programmed. It also calibrates the current read- 460VAC chillers: out under the OPER DATA key.
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 Quick Reference Programming Chart Setpoints Section Cooling Setpoints Key Schedule/ Program Mode (press key to adv.) Advance Day Key (press enter to adv.) Local Leaving Mon. – Sun. Discharge Water Temp Control &...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 UNIT KEYS OPTIONS CLOCK 00070VIP Options Key This allows both systems to run. There are many user programmable options under the OPTIONS key. The OPTIONS key is used to scroll through the list of options by repeatedly pressing the S Y S S W I T C H...
Page 132
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 Unit control is based on return chilled liquid temp. C H I L L E D L I Q U I D Return Chilled Liquid Control can only be selected on G L Y C O L units that have 4 to 6 compressors (dual system units).
Page 133
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 Option 9 – Condenser Fan Control Mode C U R R E N T F E E D B A C K O N E P E R S Y S T E M F A N C O N T R O L D I S C H A R G E...
Page 134
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 Option 15 – Refrigerant Type F L A S H C A R D U P D A T E E N A B L E D R E F R I G E R A N T T Y P E R –...
Page 135
The displays for this PUMP SELECTION option board pump kit or to control an external pump through should only appear if “YORK HYDRO KIT PUMPS = dry contacts 23 and 24 on Terminal Block XTBC2. To 2” are selected under Option 19. Presently, this option use this option, the following selection should be made should not be used.
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 Options Key Expansion Valve Type (press Options Key (Thermoplastic or Electric) to adv.) (Programmed under Service Display Language Mode, Viewable Only) Must be programmed for Thermostatic System Switches on/off Flash Card Update Chilled Liquid Type (water or glycol) Remote Temp Reset...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 BACNET, MODBUS, N2 AND YORKTALK 2 • RS-485: connect to TB2 - Network (-1) to TB2 (-1); Network (+1) to TB2 (+1) COMMUNICATIONS Data can be read and in some cases modified using a •...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 035-02550-xxx I/O Board LD14318 FIGURE 37 - MICRO PANEL CONNECTIONS The table below shows the minimum, maximum, and default values. TABLE 14 - MINIMUM, MAXIMUM AND DEFAULT VALUES DESCRIPTION MINIMUM MAXIMUM DEFAULT DE MODIFIER ADDRESS...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 The table below shows set-up requirements for each communication protocol. TABLE 15 - VALUES REQUIRED FOR BAS COMMUNICATION PROTOCOL SETTING DESCRIPTION BACNET MS/TP MODBUS RTU YORKTALK 2 DE MODIFIER ADDRESS 0 to 41943 0 to 41943 DE MODIFIER OFFSET...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 TABLE 16 - REAL TIME ERROR NUMBERS Communications Data Map Notes ERROR (See Table 17) NUMBER DESCRIPTION 1. IPU II based units are configured for Native BAC- (##) net MS/TP and Modbus RTU communications. ALL OK E-Link Gateway not required for these two com- DATUM TYPE OK TEST FAILED...
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 TABLE 17 - NATIVE BACNET, MODBUS AND N2 COMMUNICATIONS DATA MAP JOHNSON CONTROLS...
Page 142
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 TABLE 17 - NATIVE BACNET, MODBUS AND N2 COMMUNICATIONS DATA MAP (CONT’D) JOHNSON CONTROLS...
Page 143
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 TABLE 17 - NATIVE BACNET, MODBUS AND N2 COMMUNICATIONS DATA MAP (CONT’D) JOHNSON CONTROLS...
Page 144
FORM 150.72-ICOM6 SECTION 7 – UNIT CONTROLS ISSUE DATE: 12/29/2017 Yorktalk 2 Communications Transmitted Data After receiving a valid transmission from the E-Link Received Data (Control Data) Gateway, the unit will transmit either operational data The unit receives eight data values from the E-Link or history buffer data depending on the “History Buffer Gateway.
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 SECTION 8 – UNIT OPERATION Unit Operating Sequence The operating sequence described below relates to op- 7. As the load decreases below setpoint, the com- eration on a hot water start after power has been ap- pressors will be shut down in sequence.
FORM 150.72-ICOM6 SECTION 8 – UNIT OPERATION ISSUE DATE: 12/29/2017 SUCTION PRESSURE LIMIT CONTROLS If after 60 seconds of run-time the leaving chilled liq- uid temperature is still above the Setpoint High Limit, The anticipatory controls are intended to prevent the the next compressor in sequence will be energized.
FORM 150.72-ICOM6 SECTION 8 – UNIT OPERATION ISSUE DATE: 12/29/2017 TABLE 19 - SAMPLE COMPRESSOR STAGING FOR RETURN WATER CONTROL COMPRESSOR STAGING FOR RETURN WATER CONTROL 4 COMPRESSOR COOLING SETPOINT = 45 °F (7.2 °C) RANGE = 10 °F (5.6 °C) # OF COMP ON * 1+HG 45 °F...
FORM 150.72-ICOM6 SECTION 8 – UNIT OPERATION ISSUE DATE: 12/29/2017 LEAVING CHILLED LIQUID SYSTEM LEAD/ RETURN CHILLED LIQUID CONTROL LAG AND COMPRESSOR SEQUENCING (Can be used on Dual System 4, 5 and 6 Comp A Lead/Lag option may be selected to help equalize Units Only) average run hours between systems with 2 refriger- Return chilled liquid control is based on staging the...
LAG AND COMPRESSOR SEQUENCING a system. A Lead/Lag option may be selected to help equalize EVAPORATOR PUMP CONTROL AND YORK average run hours between systems with 2 refriger- HYDRO KIT PUMP CONTROL ant systems. This may be programmed under the OP- TIONS key.
DO NOT SELECT the 156 and Table 23 on page 157). The fan control on option “YORK HYDRO KIT PUMPS = 2” under the pressure and fan differential off-pressure are program- OPTIONS key. If a dual pump option is installed, the mable under the PROGRAM key.
FORM 150.72-ICOM6 SECTION 8 – UNIT OPERATION ISSUE DATE: 12/29/2017 TABLE 22 - YLAA STANDARD CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY (2, 3, OR 4 FANS PER SYSTEM) IPUII I/O OUTPUT FAN # CONTACTOR OFF** STAGE SYS 1 SYS 2 SYS 1 SYS 2 SYS 1...
Page 157
FORM 150.72-ICOM6 SECTION 8 – UNIT OPERATION ISSUE DATE: 12/29/2017 TABLE 23 - YLAA STANDARD CONDENSER FAN CONTROL USING DISCHARGE PRESSURE ONLY (5 OR 6 FANS PER SYSTEM) IPUII I/O OUTPUT FAN CONTACTOR FAN # OFF** STAGE SYS 1 SYS 2 SYS 1 SYS 2 SYS 1...
There are two ways to load limit the unit. The first is through remote communication via an ISN. Load limit stages are sent through YORK Talk on pages 9 and 10 of feature 54. Page 9 is stage 1 load limit and page 10 COMPRESSOR RUN STATUS is stage 2 load limit.
FORM 150.72-ICOM6 SECTION 8 – UNIT OPERATION ISSUE DATE: 12/29/2017 REMOTE BAS/EMS TEMPERATURE RESET If a 4 to 20mA signal is supplied, it is applied to Ter- minals A+ and A- and jumper JP1 on the I/O board USING A VOLTAGE OR CURRENT SIGNAL must be installed between pin 1 and 2.
Page 160
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 SECTION 9 – SERVICE AND TROUBLESHOOTING Following is the order of outputs that will appear as the CLEARING HISTORY BUFFERS ENTER/ADV key is pressed: The history buffers may be cleared by pressing the HISTORY key and then repeatedly pressing the UP SYS 1 COMP 1 STATUS TB7-2 IS: arrow key until you scroll past the last history buffer SYS 1 LLSV STATUS TB7-3 IS:...
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 12/29/2017 SERVICE MODE – ANALOG AND DIGITAL S Y S L L S V S T A T U S INPUTS T B 10 - 3 O F F After entering Service Mode (PROGRAM ↑↑ ↓↓), all digital and analog inputs to the microboard can be This display indicates that the system 1 liquid line sole- viewed by pressing the OPER DATA key.
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 12/29/2017 TABLE 27 - I/O ANALOG INPUTS F L O W S W / R E M S T A R T SYS 1 Suction Transducer J 13 - 5 J7-10 -or- SYS 1 Low Pressure Switch...
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 12/29/2017 CHECKING INPUTS AND OUTPUTS TABLE 29 - OUTDOOR AIR SENSOR TEMPERATURE/VOLTAGE/ Digital Inputs CORRELATION See the unit wiring diagram. All digital inputs are con- VOLTAGE TEMP °F (SIGNAL INPUT TEMP °C nected to J13-1 of the I/O board.
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 12/29/2017 Liquid and Refrigerant Sensor Test Points TABLE 30 - ENTERING/LEAVING CHILLED LIQUID TEMP. SENSOR, TEMPERATURE/ (See Table 30 on page 166) VOLTAGE CORRELATION VOLTAGE Entering Chilled Liquid Sensor TEMP °F (SIGNAL INPUT TEMP °C J6-5 = +5VDC regulated supply to sensor.
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 12/29/2017 J9-7 = +5VDC return TABLE 31 - PRESSURE TRANSDUCERS 0-400 PSIG SUCTION 0-600 PSIG DISCHARGE J9-2 = drain (shield connection = 0VDC) PRESSURE PRESSURE TRANSDUCER TRANSDUCER The suction transducers have a range from 0 to 400 PRESSURE VOLTAGE PRESSURE...
TB10 The part number for the printer that is packaged spe- SYS 2 TB10-4 COMPR 2 (5) cifically for YORK is P/N 950915576. The cable to SYS 2 TB10-5 connect the printer can either be locally assembled COMPR 3 (6)
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 12/29/2017 Assembly and Wiring Obtaining a Printout All components should be assembled and wired as A printout is obtained by pressing the PRINT key on shown in Figure 43. Strip the outside insulation back the keypad and then pressing either the OPER DATA several inches and individual wires about 3/8”...
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 12/29/2017 TROUBLESHOOTING TABLE 32 - TROUBLESHOOTING PROBLEM CAUSE SOLUTION 1. No 115VAC to 24VAC 1a. Check wiring and fuse 1FU. Transformer. 1b. Check wiring emergency stop contacts 5 to L of XTBC2 Terminal Block. 1c.
Page 171
FORM 150.72-ICOM6 SECTION 9 – SERVICE AND TROUBLESHOOTING ISSUE DATE: 12/29/2017 TABLE 32 - TROUBLESHOOTING (CONT’D) PROBLEM CAUSE SOLUTION 1. Improperly adjusted leaving 1. Re-program the leaving chilled liquid temp. chilled liquid temp. cutout (glycol cutout. only). 2. Micro panel setpoint/range 2.
Page 172
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 THIS PAGE INTENTIONALLY LEFT BLANK JOHNSON CONTROLS...
MCHX. This can cause severe damage to the level falls to the bottom limit of the oil sight glass. coils. Use YORK “V” oil 011-00949-000, when • DO NOT use a pressure washer to clean the adding oil to Copeland compressor. The MCHX.
FORM 150.72-ICOM6 SECTION 10 – MAINTENANCE ISSUE DATE: 12/29/2017 2. Rinse the MCHX with tap water. Do not use BRAZED PLATE HEAT EXCHANGER MCHX cleaners. Rinse the coil from the inside (EVAPORATOR) HEATER out, running water through every passage in the The internal power supply to the Evapo- heat exchanger surface until it is clean.
Page 175
FORM 150.72-ICOM6 SECTION 10 – MAINTENANCE ISSUE DATE: 12/29/2017 TEMPERATURE CONVERSION CHART TEMPERATURE CONVERSION CHART Temperature Conversion Chart - Temperature Conversion Chart - Actual Temperatures Differential Temperatures ° F ° C °C °F ° F ° C °C °F -17.8 -0.4 -15.6 -13.3...
Page 176
FORM 150.72-ICOM6 SECTION 10 – MAINTENANCE ISSUE DATE: 12/29/2017 R-410A PRESSURE TEMPERATURE CHART PSIG TEMP ˚F PSIG TEMP ˚F JOHNSON CONTROLS...
FORM 150.72-ICOM6 ISSUE DATE: 12/29/2017 The following factors can be used to convert from English to the most common SI Metric values. TABLE 33 - SI METRIC CONVERSION MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity Tons Refrigerant Effect (ton) 3.516 Kilowatts (kW) Power...