York YLAA Operation Manual

York YLAA Operation Manual

Air-cooled scroll chillers with brazed plate heat exchangers

Advertisement

FORM 150.72-EG6 (516)
MODEL YLAA
AIR-COOLED SCROLL CHILLERS
WITH BRAZED PLATE HEAT EXCHANGERS
STYLE B
55 – 175 TON
195 – 615 kW
60 Hz
R-410A

Advertisement

Table of Contents
loading

Summary of Contents for York YLAA

  • Page 1 FORM 150.72-EG6 (516) MODEL YLAA AIR-COOLED SCROLL CHILLERS WITH BRAZED PLATE HEAT EXCHANGERS STYLE B 55 – 175 TON 195 – 615 kW 60 Hz R-410A...
  • Page 2 FOUR DIGIT UNIT NUMBER A = AMERICAS A = AIR COOLED YL = YORK CHILLER Approvals • ASME Boiler and Pressure Vessel Code – Section Vlll Division 1. • AHRI Standard 550/590 and 551/591. • UL 1995 – Heating and Cooling Equipment • ASHRAE 15 –...
  • Page 3: Table Of Contents

    FORM 150.72-EG6 (516) Table Of Contents INTRODUCTION ..............................5 EQUIPMENT OVERVIEW ............................8 UNIT COMPONENTS ............................15 ACCESSORIES AND OPTIONS ........................... 16 DESIGN PARAMETERS ............................20 WATER PRESSURE DROP ........................... 21 PHYSICAL DATA AND NOMINAL RATINGS ......................22 PART LOAD RATINGS ............................24 UNIT DIMENSIONS ..............................
  • Page 4 FORM 150.72-EG6 (516) THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS...
  • Page 5: Introduction

    The YLAA weighs less and has s smaller footprint than other chillers in its class. In fact, it is 20-35% lighter weight than the market average chiller. When the chiller is roof-mounted in new construction, the cost of the support structure can be reduced.
  • Page 6 YLAA also offers an efficiency choice. In addition to the high-efficiency units, YLAA chill- ers are available in standard efficiency models with smaller footprints and lower capital costs. Only pay for the chiller you need – the multi-efficiency levels of the YLAA allow you to decide the best investment for the job. Flexibility The YLAA chiller offers a number of options designed to operate reliably across a wide range of customer needs.
  • Page 7 Minimal maintenance is required to keep the unit operating at maximum performance. If service should ever be required, the YLAA chiller has been designed to simplify the work, keeping costs down. The layout of the chiller locates all the major components that can be serviced near the outside edge.
  • Page 8: Equipment Overview

    FORM 150.72-EG6 (516) Equipment Overview The 55 - 175 Ton (195 - 615 kW) YLAA models are shipped complete from the factory ready for installa tion and use. The unit is pressure-tested, evacuated, and fully charged with a zero Ozone Depletion Potential Refrigerant R-410A and includes an initial oil charge. After assembly, a complete operational test is performed with water flowing through the evapo- rator to as sure that the refrigeration circuit operates correctly.
  • Page 9 FORM 150.72-EG6 (516) Equipment Overview (Cont'd) BRAZED PLATE EVAPORATOR The compact, high efficiency Brazed Plate Heat Exchanger (BPHE) is constructed with 316L stainless steel corrugated channel plates with a filler material between each plate. It offers excellent heat transfer performance with a compact size and low weight, reducing structural steel requirements on the job site.
  • Page 10 CANADIAN REGISTRATION NUMBER (CRN) APPLICATION & PROOF OF CONFORMANCE Reference Table 1 for YLAA brazed plate evaporator Canadian Registration Numbers (CRN) for all Canadian Provinces. All YLAA brazed plate evaporators are categorized as pressure “H” fittings per CSA-B51. TABLE 1 - CANADIAN REGISTRATION NUMBERS...
  • Page 11 They feature ball bearings that are double-sealed and permanently lu bricated. UNIT CONTROL SYSTEM The YLAA chiller is designed with an intelligent control system that operates the chiller automatically with maximum reliability, safety and ease of use. The controls are factory tested and with as little user input as a chilled liquid setpoint the chiller will operate to meet the load demand.
  • Page 12 FORM 150.72-EG6 (516) Equipment Overview (Cont'd) Maximum reliability is achieved through intelligent control. Run hours and starts are av- eraged across all compressors automatically, and between both pumps of the optional dual pump hydro-kit. When compressors are cycled off, an anti-recycle timer ensures the motors have time to cool before starting again, for the maximum service life.
  • Page 13 FORM 150.72-EG6 (516) Equipment Overview (Cont'd) • Number of compressors • Low liquid temperature cut-out • Low suction pressure cut-out • High discharge pressure cut-out • Anti-recycle timer (compressor start cycle time) • Anti-coincident timer (delay compressor starts) UNIT section to: • Set time • Set unit options In addition, the microprocessor control center is capable of displaying the following data...
  • Page 14 • Optional communication available for LON via eLink option BUILDING AUTOMATION SYSTEM INTERFACE In addition to native BACnet, Modbus and N2, the YLAA chiller accepts a 4-20 milliamp or 0-10VDC input to reset of the leaving chilled liquid temperature. The standard unit ca- pabilities include remote start-stop, remote water temperature reset via up to two steps of demand (load) limiting depending on model.
  • Page 15: Unit Components

    FORM 150.72-EG6 (516) Unit Components MICROCHANNNEL FAN DECK COILS COIL HEADERS HYDRO-KIT PUMPS AND CONTROL MOTORS (OPTIONAL) POWER PANELS COMPRESSORS FORMED STEEL BRAZED PLATE BASE RAILS EVAPORATOR LD18426 FIGURE 1 - GENERAL UNIT COMPONENTS JOHNSON CONTROLS...
  • Page 16: Accessories And Options

    FORM 150.72-EG6 (516) Accessories and Options All options are factory installed unless otherwise noted. POWER OPTIONS: Unit Power Connections – Single-point terminal block connection(s) are provided as stan- dard. The following power connections are available as options. (See electrical data for specific voltage and options availability.) Single-Point Supply Terminal Block –...
  • Page 17 FORM 150.72-EG6 (516) Accessories and Options (Cont'd) COMPRESSOR, PIPING, EVAPORATOR OPTIONS: Low Temperature Glycol – Replaces standard Thermostatic Expansion Valves with Elec- tronic Expansion Valves to achieve leaving glycol temperatures as low as 10°F (-12°C). Re- quired for any leaving liquid temperature below 30°F (-1°C). Electronic Expansion Valves permit operation at both low temperatures and comfort cooling applications without a capac- ity loss or derate at either condition.
  • Page 18 FORM 150.72-EG6 (516) Accessories and Options (Cont'd) CONDENSER AND CABINET OPTIONS: Condenser coil protection against corrosive environments is available by choosing any of the following options. For additional application recommendations, refer to FORM 150.12- ES1. Post-Coated Condenser Coils – The unit is built with electrostatic post-coated condenser coils.
  • Page 19 FORM 150.72-EG6 (516) Accessories and Options (Cont'd) SOUND ATTENUATION: One or both of the following sound attenuation options are recommended for residential or other similar sound sensitive locations. Compressor Acoustic Sound Blanket – Each compressor is individually enclosed by an acoustic sound blanket.
  • Page 20: Design Parameters

    FORM 150.72-EG6 (516) Design Parameters NOMINAL EVAPORATOR WATER FLOW TEMPERATURE (°F) WATER FLOW (GPM) AIR ON CONDENSER (°F) YLAA STANDARD EFFICIENCY 0070SE 0080SE 0089SE 0100SE 0120SE 0136SE 0155SE 0170SE HIGH EFFICIENCY 0058HE 0065HE 0081HE 0092HE 0101HE 0125HE 0142HE 0156HE 0175HE NOTES: 1.
  • Page 21: Water Pressure Drop

    FORM 150.72-EG6 (516) Water Pressure Drop YLAA EVAPORATOR PRESSURE DROP CURVE LD18432 WATER FLOW RATE (GPM) EVAPORATOR YLAA MODELS 0058HE, 0065HE, 0070SE 0080SE 0089SE, 0100SE, 0092HE, 0101HE, 0125HE 0081HE, 0136SE, 0170SE, 0156HE 0120SE, 0155SE, 0142HE 0175HE JOHNSON CONTROLS...
  • Page 22: Physical Data And Nominal Ratings

    FORM 150.72-EG6 (516) Physical Data and Nominal Ratings YLAA REFRIGERANT R-410A STANDARD EFFICIENCY UNITS 0070SE 0080SE 0089SE 0100SE 0120SE 0136SE 0155SE 0170SE NOMINAL RATINGS TONS 71.0 77.8 81.8 95.6 118.1 126.1 143.0 167.4 77.5 86.3 93.0 111.5 134.6 142.6 165.0 192.1...
  • Page 23 FORM 150.72-EG6 (516) Physical Data and Nominal Ratings (Cont'd) YLAA REFRIGERANT R-410A HIGH EFFICIENCY UNITS 0058HE 0065HE 0081HE 0092HE 0101HE 0125HE 0142HE 0156HE 0175HE NOMINAL RATINGS TONS 57.0 62.3 78.8 85.7 98.3 116.0 129.5 144.5 172.5 64.4 71.9 91.0 83.6 106.1...
  • Page 24: Part Load Ratings

    FORM 150.72-EG6 (516) Part Load Ratings STANDARD EFFICIENCY YLAA0070SE YLAA0136SE COMPR. COMPR. AMBIENT UNIT AMBIENT UNIT % DISPL. TONS % DISPL. TONS (°F) (°F) 100.0 126.1 142.6 95.0 100.0 71.0 75.5 95.0 10.4 83.3 108.0 91.9 86.4 12.2 83.3 62.8 56.2 88.1 12.0...
  • Page 25 FORM 150.72-EG6 (516) Part Load Ratings (Cont'd) HIGH EFFICIENCY YLAA0058HE YLAA0125HE COMPR. COMPR. AMBIENT UNIT AMBIENT UNIT % DISPL. TONS % DISPL. TONS (°F) (°F) 100.0 57.0 57.7 95.0 10.6 100.0 116.0 112.0 95.0 10.3 75.0 46.2 36.6 83.7 12.8 75.0 94.6 76.8...
  • Page 26: Unit Dimensions

    FORM 150.72-EG6 (516) Unit Dimensions YLAA0058HE, YLAA0065HE, YLAA0081HE 3” INLET 3” OUTLET LD18432 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli- able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;...
  • Page 27 FORM 150.72-EG6 (516) Unit Dimensions (Cont'd) YLAA0070SE, YLAA0080SE, YLAA0089SE LD18433 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli- able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;...
  • Page 28 FORM 150.72-EG6 (516) Unit Dimensions (Cont'd) YLAA0100SE LD18434 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli- able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;...
  • Page 29 FORM 150.72-EG6 (516) Unit Dimensions (Cont'd) YLAA0120SE, YLAA0092HE, YLAA0101HE LD18435 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli- able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;...
  • Page 30 FORM 150.72-EG6 (516) Unit Dimensions (Cont'd) YLAA0125HE, YLAA 0136SE, YLAA0155SE, YLAA0142HE LD18436 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli- able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;...
  • Page 31 FORM 150.72-EG6 (516) Unit Dimensions (Cont'd) YLAA 0170SE, YLAA0156HE, YLAA0175HE LD18437 NOTE: Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli- able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow patterns and possible diminished performance. The unit controls will optimize operation without nuisance high-pressure safety cut-outs;...
  • Page 32: Isolator Locations

    FORM 150.72-EG6 (516) Isolator Locations FOUR FAN ISOLATOR LOCATIONS YLAA0058HE, YLAA0065HE, YLAA0081HE LD19400 FOUR FAN ISOLATOR LOCATIONS YLAA0070SE, YLAA0080SE, YLAA0089SE LD18438 All dimensions are inches unless otherwise specified. Dimensions indicate isolator mounting centerlines. JOHNSON CONTROLS...
  • Page 33 FORM 150.72-EG6 (516) Isolator Locations (Cont'd) FIVE & SIX FAN ISOLATOR LOCATIONS YLAA0100SE, YLAA0120SE, YLAA0092HE, YLAA0101HE LD18439 VIEW EIGHT FAN ISOLATOR LOCATIONS YLAA0125HE, YLAA 0136SE, YLAA0155SE, YLAA0142HE LD18440 VIEW All dimensions are inches unless otherwise specified. Dimensions indicate isolator mounting centerlines. JOHNSON CONTROLS...
  • Page 34 FORM 150.72-EG6 (516) Isolator Locations (Cont'd) TEN FAN ISOLATOR LOCATIONS YLAA 0170SE, YLAA0156HE, YLAA0175HE LD18441 VIEW All dimensions are inches unless otherwise specified. Dimensions indicate isolator mounting centerlines. JOHNSON CONTROLS...
  • Page 35 FORM 150.72-EG6 (516) THIS PAGE INTENTIONALLY LEFT BLANK. JOHNSON CONTROLS...
  • Page 36: Isolator Details

    FORM 150.72-EG6 (516) Isolator Details TWO INCH DEFLECTION, SPRING ISOLATOR (Y2RS-) 1-1/8” 5/8” 2-3/4” 2-3/4” 3/8” GAP 3/4” TYP. (4) 3/4” 7/8” STOP & 8-3/8” OPER. HEIGHT LD18442 MODEL Y2RSI-2D RESTRAINED VIBRATION ISOLATOR FOR 2" DEFLECTION RATED ALLOWABLE RATED LOAD SPRING RATE SOLID LOAD MOUNT...
  • Page 37 FORM 150.72-EG6 (516) Isolator Details (Cont'd) ONE INCH DEFLECTION SPRING ISOLATOR (CPX-X-) EQUIPMENT BASE (BY OTHERS) POSITIONING LD18443 DIMENSION DATA INCHES (MM) MOUNT 3 (76) 0.625 (16) 7.75 (197) 6.5 (165) 4.75 (121) 0.5 (13) 4.625 (117) 3 (76) 0.625 (16) 10.5 (267) 9.25 (235) 7.75 (197) 0.5625 (14) 6 (152) DEFLECTION RATED CAPACITY...
  • Page 38 FORM 150.72-EG6 (516) Isolator Details (Cont'd) ELASTOMERIC ISOLATOR ISOLATORS ISOLATORS MOLDED DURULENE MOLDED DURULENE Ø = AD Thru Typ 2 Places R = 0.280 Slot Typ 2 Places LD17304 MOUNT DIMENSION DATA INCHES (MM) TYPE 3.38 2.88 4.13 0.56 0.25 RD3-WR 1/2-13 UNC X 1 (139.7)
  • Page 39: Electrical Notes

    FORM 150.72-EG6 (516) Electrical Notes NOTES: 1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the cir- cuit, per N.E.C. Article 430-24. If the optional Factory Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system providing power to the transformer: -17, add 2.5 amps;...
  • Page 40 FORM 150.72-EG6 (516) Electrical Notes (Cont'd) LEGEND ACR-LINE ACROSS THE LINE START C.B. CIRCUIT BREAKER D.E. DUAL ELEMENT FUSE DISC SW DISCONNECT SWITCH FACT MOUNT CB FACTORY MOUNTED CIRCUIT BREAKER FULL LOAD AMPS HERTZ MAXIMUM MINIMUM CIRCUIT AMPACITY MINIMUM MIN NF MINIMUM NON FUSED RATED LOAD AMPS S.P.
  • Page 41: Variable Speed Pump Electrical Data

    FORM 150.72-EG6 (516) Variable Speed Pump Electrical Data PUMP ELECTRICAL DATA HORSE PUMP 208V-3-60HZ 230V-3-60HZ 380V-3-60HZ 460V-3-60HZ 575V-3-60HZ POWER 3600 15.4 3600 23.2 18.4 11.1 3600 28.3 15.1 1800 3600 12.9 36.4 10.9 18.2 14.6 3600 23.2 18.4 11.1 3600 28.3 15.1 3600...
  • Page 42: Wiring Lugs

    SINGLE POINT MOLDED CASE MOLDED CASE SUPPLY GLOBAL MARKET SWITCH SINGLE CIRCUIT BREAKER TERMINAL POINT SUPPLY SINGLE POINT SUPPLY YLAA BLOCK INSTALLED INSTALLED INSTALLED ALTERNATE ALTERNATE VOLTS (1) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400...
  • Page 43 SINGLE POINT MOLDED CASE MOLDED CASE SUPPLY GLOBAL MARKET SWITCH SINGLE CIRCUIT BREAKER TERMINAL POINT SUPPLY SINGLE POINT SUPPLY YLAA BLOCK INSTALLED INSTALLED INSTALLED ALTERNATE ALTERNATE VOLTS (2) # 6 - 500 (2) 250 - 500 (3) 2/0 - 400...
  • Page 44: Electrical Data Without Pumps

    FORM 150.72-EG6 (516) Electrical Data Without Pumps SYSTEM # 1 DUAL DUAL COMPR 1 COMPR 2 COMPR 3 STD FLOW FANS YLAA VOLT ELEM DISC ELEM FUSE & CB 57.7 57.7 57.7 57.7 30.9 30.9 23.1 26.9 26.9 21.5 21.5 15.3...
  • Page 45 FORM 150.72-EG6 (516) Electrical Data Without Pumps (Cont'd) SYSTEM # 2 DUAL DUAL COMPR 1 COMPR 2 COMPR 3 STD FLOW FANS YLAA VOLT ELEM ELEM DISC FUSE FUSE & CB & CB LRA QTY 57.7 57.7 57.7 57.7 30.9 30.9...
  • Page 46 FORM 150.72-EG6 (516) Electrical Data Without Pumps (Cont'd) SYSTEM # 1 DUAL DUAL COMPR 1 COMPR 2 COMPR 3 STD FLOW FANS YLAA VOLT ELEM DISC ELEM FUSE & CB 57.7 57.7 57.7 57.7 57.7 57.7 30.9 30.9 30.9 23.1 26.9...
  • Page 47 FORM 150.72-EG6 (516) Electrical Data Without Pumps (Cont'd) SYSTEM # 2 DUAL DUAL COMPR 1 COMPR 2 COMPR 3 STD FLOW FANS YLAA VOLT ELEM ELEM DISC FUSE FUSE & CB & CB LRA QTY 106.2 106.2 106.2 106.2 64.3 64.3...
  • Page 48: Wiring Diagram

    FORM 150.72-EG6 (516) Wiring Diagram JOHNSON CONTROLS...
  • Page 49 FORM 150.72-EG6 (516) Wiring Diagram (Cont'd) LD18444 JOHNSON CONTROLS...
  • Page 50 FORM 150.72-EG6 (516) Wiring Diagram (Cont'd) MANUAL MOTOR STARTER COMP ENTERING CHILLED TEMP MOTOR PROTECTOR COMP FIELD MOUNTED AND WIRED ON REMOTE EVAP UNITS ARE NOT SUPPLIED BY JOHNSON CONTROLS JOHNSON CONTROLS...
  • Page 51 FORM 150.72-EG6 (516) Wiring Diagram (Cont'd) This drawing is based on IEC symbols. Field wiring to be in accordance with the relevant electrical code as well as all other applicable codes and specifications All sources of supply shown on this diagram to be taken from one main isolator, not shown or supplied by the chiller manufacturer .
  • Page 52: User Control Wiring

    FORM 150.72-EG6 (516) User Control Wiring USER CONTROL WIRING INPUTS INTERNAL WIRING TO OPTIONAL REMOTE TEMP. RESET BOARD FLOW SWITCH REMOTE UNLOAD STEP 1 PWM REMOTE TEMP RESET INTERNAL WIRING TO 2-KCR CONTROL RELAY INTERNAL WIRING TO 1-KCR CONTROL RELAY REMOTE START / STOP XTBC1 LD13130...
  • Page 53: Application Data

    Application Data UNIT LOCATION The YLAA chillers are designed for outdoor installation. When selecting a site for installa- tion, be guided by the following conditions: A. For outdoor locations of the unit, select a place having an adequate supply of fresh air for the condenser.
  • Page 54 There are many other design issues to evaluate with variable primary flow systems. Consult your Johnson Controls Sales Office for more information about successfully applying YLAA chillers. CHILLED LIQUID PIPING The chilled liquid piping system should be laid out so that the circulating pump discharges into the evaporator.
  • Page 55: Guide Specifications

    FORM 150.72-EG6 (516) Guide Specifications PART 1 – GENERAL 1.01 SCOPE A. The requirements of this Section shall conform to the general provisions of the Con- tract, including General and Supplementary Conditions, Conditions of the Contract, and Contract Drawings. B. Provide microprocessor-controlled, multiple-scroll compressor, air-cooled, liquid chill- ers of the scheduled capacities as shown and indicated on the drawings, including but not limited to: 1.
  • Page 56 FORM 150.72-EG6 (516) Guide Specifications (Cont'd) B. Factory Run Test: Chiller shall be pressure-tested, evacuated and fully charged with re- frigerant and oil, and shall be factory operational run tested with water flowing through the vessel. C. Chiller manufacturer shall have a factory trained and supported service organization. D. Warranty: Manufacturer shall Warrant all equipment and material of its manufacture against defects in workmanship and material for a period of eighteen (18) months from date of shipment or twelve (12) months from date of start-up, whichever occurs first.
  • Page 57 FORM 150.72-EG6 (516) Guide Specifications (Cont'd) 3. High Ambient Control: Allows units to operate when the ambient temperature is above 115°F (46°C). Includes discharge pressure transducers. 2.02 COMPRESSORS A. Compressors: Shall be hermetic, scroll-type, including: 1. Compliant design for axial and radial sealing 2.
  • Page 58 FORM 150.72-EG6 (516) Guide Specifications (Cont'd) 6. A 20 mesh, serviceable wye-strainer and mechanical couplings shall be provided for field installation on evaporator inlet prior to startup. [Option] Evaporator shall be provided with piping extension kit and mechanical couplings to extend liquid connection from evaporator to edge of unit. Thermal dispersion type flow switch shall be factory installed in the evaporator outlet pipe extension and wired to the unit control panel.
  • Page 59 FORM 150.72-EG6 (516) Guide Specifications (Cont'd) 5. Programmable Setpoints (within Manufacturer limits): display language; chilled liq- uid temperature setpoint and range, remote reset temperature range, daily sched- ule/holiday for start/stop, manual override for servicing, low and high ambient cut- outs, low liquid temperature cut-out, low suction pressure cut-out, high discharge pressure cut-out, anti-recycle timer (compressor start cycle time), and anti-coinci- dent timer (delay compressor starts).
  • Page 60 FORM 150.72-EG6 (516) Guide Specifications (Cont'd) B. Compressor, control and fan motor power wiring shall be located in an enclosed panel or routed through liquid tight conduit. 2.07 ACCESSORIES AND OPTIONS Some accessories and options supercede standard product features. Your Johnson Con- trols representative will be pleased to provide assistance.
  • Page 61 FORM 150.72-EG6 (516) Guide Specifications (Cont'd) 3. Louvered Panels (full unit): painted steel as per remainder of unit cabinet, to protect condenser coils from incidental damage, visually screen internal components, and prevent unauthorized access to internal components. 4. Louvered/Wire Panels: louvered steel panels on external condenser coils painted as per remainder of unit cabinet.
  • Page 62 FORM 150.72-EG6 (516) Guide Specifications (Cont'd) PART 3 – EXECUTION 3.01 INSTALLATION A. General: rig and install in full accordance with manufacturer’s requirements, project drawings, and contract documents. B. Location: locate chiller as indicated on drawings, including cleaning and service main- tenance clearance per manufacturer instructions.
  • Page 63: Si Metric Conversion

    FORM 150.72-EG6 (516) SI Metric Conversion Values provided in this manual are in the English inch-pound (I-P) system. The following factors can be used to convert from English to the most common Sl Metric values. MULTIPLY THIS TO OBTAIN THIS MEASUREMENT ENGLISH VALUE METRIC VALUE...
  • Page 64 Printed on recycled paper Form 150.72-EG6 (516) Supersedes: 150.72-EG6 (416) © 2016 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53201 Printed in USA www.johnsoncontrols.com Issued on 05/25/2016...