3 - OPERATION LIMITS

Series
Air
Max.
30PA
46ºC
With control of the condensation pressure operating up to -15ºC.
Minimum outlet temperature. With the option of glycol water for
lower temperature operation from 5ºC to -7ºC.

4 - AVAILABLE CONFIGURATIONS

According to the air supply:
■ Assembly M00
HORIZONTAL air supply.
■ Assembly M01
VERTICAL air supply.
M00
4
Cooling mode
Water (outlet T.)
Min.
Max.
Min.
18ºC
12ºC
5ºC
M01
+46
+12
-15
According to the type of supply fan:
■ STD version (Standard):
Centrifugal fan coupling by pulleys and belts.
■ HEE version (High Energy Effi ciency):
Variable speed electronic plug-fan.
Mandatory glycol
-7
0
+5
Outlet water temp. in the evaporator °C
STD
+18
HEE