7 - LOCATION AND ASSEMBLING

Anchorage for silent-blocks

Distances (mm)
30PA
A
B
C
90STD
896
760
65
100STD
896
760
65
120STD
1166
760
65
160STD
1166
760
65
180STD
1166
760
65
90HEE
896
760
65
100HEE
1166
760
65
120HEE
1166
760
65
160HEE
1892
760
65
180HEE
1892
760
65
Note: all the anchorings are bolt and nut type.

Sound level

These units have been designed to operate with a low sound level.
In any case, in the design of the installation, it must be taken into
consideration: the outdoor environment for the acoustic radiation,
the type of building for the noise transmitted in the air and the solid
elements for the vibration transmission.
To reduce the transmissions through solid matter to the maximum,
we recommend installing damping devices between the fl oor or
structure and the frame of the unit and fl exible connections in the
hydraulic tubes.
If necessary, an acoustic technician must commission a study.
Reactions in the supports (kg)
Weight in
R1
R2
R3
service
306
66
101
87
315
69
93
84
379
89
112
101
397
92
119
107
396
93
119
105
298
64
100
85
358
63
127
116
376
88
112
100
465
69
177
163
468
71
178
163
Radiated sound power level
Measurement conditions: ducted discharge and return. For nominal
operating conditions EN 14511 – Acoustic power reference: 10E-12
W, tolerance of ±2 dB (partial charge of ±4 dB).
R4
52
30PA
60
63 Hz
dB(lin)
77
125 Hz
dB(lin)
79
250 Hz
dB(lin)
79
500 Hz
dB(lin)
50
1000 Hz
dB(lin)
52
2000 Hz
dB(lin)
77
4000 Hz
dB(lin)
56
8000 Hz
dB(lin)
Total
dB(A)
56
30PA
63 Hz
dB(lin)
125 Hz
dB(lin)
250 Hz
dB(lin)
500 Hz
dB(lin)
1000 Hz
dB(lin)
2000 Hz
dB(lin)
4000 Hz
dB(lin)
8000 Hz
dB(lin)
Total
dB(A)
Note: The unit has acoustic insulating cover for compressor (Low
Noise version).
Ducted sound power level
Measurement conditions: ducted discharge and return. For nominal
operating conditions EN 14511 – Acoustic power reference: 10E-12
W, tolerance of ±2 dB (partial charge of ±4 dB).
30PA
Total
dB(A)
30PA
Total
dB(A)
Sound pressure level
Measurement conditions: in a clear fi eld, measured at a distance
of 10 metres, directivity 2 and at 1,5 metres from the ground.
30PA
Total
dB(A)
30PA
Total
dB(A)
Note: The sound pressure level depends on the installation
conditions and, as such, is only indicated as a guide. Values
obtained according to standard ISO 3744.
STD version
90STD
100STD 120STD 160STD 180STD
73,8
74,2
74,4
73,2
73,6
73,8
70,2
70,6
70,8
65,3
65,7
65,9
63,0
63,4
63,6
62,2
62,6
62,8
58,2
58,6
58,8
49,3
49,7
49,9
69,4
69,8
70,0
HEE version
90HEE
100HEE 120HEE 160HEE 180HEE
71,1
73
73,1
70,9
72,8
72,9
67,5
69,4
69,5
65,4
67,3
67,4
62,4
64,3
64,4
59,5
61,3
61,5
56,5
58,4
58,5
49,4
51,3
51,4
68,0
69,9
70,0
STD version
90STD
100STD 120STD 160STD 180STD
83,0
84,0
84,0
HEE version
90HEE
100HEE 120HEE 160HEE 180HEE
82,0
84,0
84,0
STD version
90STD
100STD 120STD 160STD 180STD
38,0
38,4
38,4
HEE version
90HEE
100HEE 120HEE 160HEE 180HEE
36,6
38,3
38,4
74,4
74,4
73,8
73,8
70,8
70,8
65,9
65,9
63,6
63,6
62,8
62,8
58,8
58,8
49,9
49,9
70,0
70,0
73,1
73,1
72,9
72,9
69,5
69,5
67,4
67,4
64,4
64,4
61,5
61,4
58,5
58,5
51,4
51,4
70,0
70,0
84,0
84,0
84,0
84,0
38,4
38,4
38,4
38,4
7