8 - CHECKING BEFORE COMMISSIONING

Air ducts connections

For units designed for installation indoors with ducted supply and
return in the outdoor circuit, it is advisable to have the following
recommendations:
■ Curves in the fan discharge supply must be avoided. It is
recommendable to have a straight section of duct measuring
approximately 1 metre. If it is not possible, they must be as
smooth as possible, using indoor defl ectors when the duct is
of large dimensions.
■ When making the ducts, direction sharp changes must be
avoided since they can generate occasional pressure drops,
which aff ect the available pressure and the fl ow. The location
of discharge and aspiration grilles must be studied carefully to
avoid the air recirculation and the transmission and generation
of noises to the interior.
■ No matter the type of ducts type to use, these must be insulated
and must not be composed of materials that propagate fi re nor
expel toxic gases in the event of a fi re. The internal surfaces
must be smooth and should not pollute the air that circulates
within them. In any case, the eff ective legislation about this
issue must be respected.
■ Flexible connections must be made between the ducts and the
unit that avoid the noise and vibration transmission.
Flexible connections
Optionally, these units can be sent with fl exible connections for
supply and return air.
Supply ducts
STD version
M00 dimensions (mm)
A
90STD / 100STD
859
120STD to 180STD
1139
STD version
M00 dimensions (mm)
A
90STD / 100STD
859
120STD to 180STD
1139
M00 dimensions (mm)
HEE version
A
90HEE
859
100HEE / 120HEE
1139
160HEE / 180HEE
1854
Damper for condensation pressure control (optional): add the
height of the damper to the fl exible duct.
In case of asking together for fl exible connections and damper
for condensation pressure control (optional for version STD),
discharge fl exible ducts are attached to the above mentioned
damper.
If it is removed the damper for installation on duct, it is necessary
to maintain the frame for reconnecting the fl exible connections.
10
Without damper
M01 dimensions (mm)
B
C
A
B
407
132
552
430
481
132
652
552
With damper
M01 dimensions (mm)
B
C
A
B
407
132
513
391
481
132
613
513
M01 dimensions (mm)
B
C
A
B
407
132
633
589
481
132
817
639
407
132
1619
590
Return ducts
STD version
90STD / 100STD
120STD to 180STD
HEE version
90HEE
100HEE / 120HEE
160HEE / 180HEE
C
M00 asssembly:
Horizontal supply
152
152
C
132
132
C
132
132
132
M01 asssembly:
Vertical supply
Without fi lters (mm)
With fi lters (mm)
C
D
E
C
132
903
800
109
132
1183
950
109
Without fi lters (mm)
With fi lters (mm)
C
D
E
C
132
903
800
109
132
1183
950
109
132
1897
800
109
D
E
903
800
1183
950
D
E
903
800
1183
950
1897
800

Advertisement

Table of Contents
loading

This manual is also suitable for:

30pa 180

Table of Contents