OPERATING LIMITS

i-BX-N operation in HEATING mode and for DOMESTIC HOT WATER PRODUCTION
65
60
55
50
45
40
35
30
25
20
-25
-20
Operation in heating mode:
System circuit temperature difference, minimum 4°k, maximum 10°k
Maximum glycol content 40%
Maximum water inlet temperature at plate heat exchanger +50°C with temperature difference of 10°k
Minimum water inlet temperature at plate heat exchanger +20°C
i-BX-N operation in COOLING mode
20
18
15
10
5
0
-5
-8
-10
0
Operation in cooling mode:
System circuit temperature difference, minimum 3°k, maximum 8°k
Maximum glycol content 40%
-15
-10
-5
0
Air intake temperature [°C]
OPERATING RANGE WITH WATER-GLYCOL MIXES
5
10
15
20
Air intake temperature [°C]
5
10
15
20
25
25
30
35
30
35
40
45
50
40
45
50
EN i-BX-(Y)_i-BX-N-(Y)
I A
I A
35