Specifications - Omron Supergate 8615 Quick Start Manual

Supergate 8615
Table of Contents

Advertisement

K3NC

Specifications

Ratings
Supply voltage
Operating voltage range
Power consumption (see note)
Sensor power supply
Insulation resistance
Dielectric withstand voltage
Noise immunity
Vibration resistance
Shock resistance
Ambient temperature
Ambient humidity
Ambient atmosphere
EMC
Approved standards
Weight
Note: An Intelligent Signal Processor with DC supply voltage requires approximately 1 A DC as control power supply current the moment the
Intelligent Signal Processor is turned on. Do not forget to take this into consideration when using several Intelligent Signal Processors.
When the Intelligent Signal Processor is not in measuring operation (e.g., the Intelligent Signal Processor has been just turned on or is
operating for startup compensation time), the display will read "00000" and all outputs will be OFF.
Input/Output Ratings
Relay Contact Output
(Incorporating a G6B Relay)
Item
Rated load
Rated carry current
Max. contact voltage
Max. contact current
Max. switching capacity
Min. permissible load
(P level, reference value)
Mechanical life
Electrical life
(at an ambient temperature of 23 C)
Transistor Output
Rated load voltage
Max. load current
Leakage current
4
100 to 240 VAC (50/60 Hz); 12 to 24 VDC
85% to 110% of supply voltage
15 VA max. (max. AC load with all indicators lit)
10 W max. (max. DC load with all indicators lit)
80 mA at 12 VDC 10%
20 MΩ min. (at 500 VDC) between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
2,000 VAC for 1 min between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
1,500 V on power supply terminals in normal or common mode 1 µs, 100 ns for
square-wave noise with 1 ns
Malfunction: 10 to 55 Hz, 0.5-mm for 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 0.75-mm for 2 hrs each in X, Y, and Z directions
2
Malfunction: 98 m/s
(10G) for 3 times each in X, Y, and Z directions
2
Destruction: 294 m/s
(30G) for 3 times each in X, Y, and Z directions
Operating: –10 C to 55 C (with no icing)
Storage:
–20 C to 65 C (with no icing)
Operating: 25% to 85% (with no condensation)
Must be free of corrosive gas
Emission Enclosure:
Emission AC Mains:
Immunity ESD:
Immunity-RF-interference:
Immunity Conducted Disturbance:
Immunity Burst:
UL508, CSA22.2; conforms to EN50081-2, EN50082-2, EN61010-1 (IEC1010-1); conforms to
VDE106/part 100 (Finger Protection) when the terminal cover is mounted.
Approx. 400 g
Resistive load (cosφ = 1)
5 A at 250 VAC; 5 A at 30 VDC
5 A max. (at COM terminal)
380 VAC, 125 VDC
5 A max. (at COM terminal)
1,250 VA, 150 W
10 mA at 5 VDC
50,000,000 times min. (at a switching frequency of 18,000 times/hr)
100,000 times min. (at a rated load switching frequency of 1,800 times/hr)
+10%
12 to 24 VDC
/
–15%
50 mA
100 µA max.
EN55011 Group 1 class A
EN55011 Group 1 class A
EN61000-4-2:4-kV contact discharge (level 2)
8-kV air discharge (level 3)
ENV50140:
10 V/m (amplitude modulated, 80 MHz to
1 GHz) (level 3)
10 V/m (pulse modulated, 900 MHz)
ENV50141:
10 V (0.15 to 80 MHz) (level 3)
EN61000-4-4:2-kV power-line (level 3)
2-kV I/O signal-line (level 4)
Inductive load (cosφ = 0.4, L/R = 7 ms)
1.5 A at 250 VAC, 1.5 A at 30 VDC
375 VA, 80 W
K3NC

Advertisement

Table of Contents
loading

Table of Contents