Motorized Combustion Air Dampers - Patterson-Kelley MACH C-1500H Installation & Owner's Manual

Gas fired boilers w/ nuro control system
Table of Contents

Advertisement

Sizing the Combustion Air Intake Ductwork
The combustion air flow rate requirements per boiler model are summarized in Section 3.4.3. When
sizing the combustion air intake ductwork, the pressure drop through this ductwork MUST NOT exceed
0.22" W.C. as described in the table below:
®
P-K MACH
Boiler Model
C-1500H, C-2000H, C-2500,
C-3000 & C-4000
C-1500H, C-2000H, C-2500,
C-3000 & C-4000
If the combustion air intake ductwork and the exhaust vent terminate on the same wall of
NOTE:
the building, they must utilize the same type of termination fitting.
Patterson-Kelley recommends including a motorized combustion air damper in each
NOTE:
appliance's air intake ductwork. Refer to Section

3.4.5 Motorized Combustion Air Dampers

Patterson-Kelley recommends, and most
installation codes require, the use of motorized
combustion air dampers with end limit switches
installed in the combustion air intake ductwork
upstream of each appliance. This damper isolates
the combustion air supply when the appliance is in
standby. Once the appliance receives a call for
heat, the motorized combustion air damper opens
and the end limit switch must close before the
appliance can proceed to ignition. Patterson-
Kelley offers motorized combustion air dampers
with built-in end limits switches for sale, which are
summarized in the table below:
Table of Recommended Motorized Combustion Air Dampers
Combustion Air Ductwork
Size
12"
14"
These normally-closed motorized combustion air dampers operate on 120 VAC and feature a built in
end limit switch which must be wired to the appliances' Air Damper Interlock circuit. Upon a call for
heat, the boiler's Air Damper Relay energizes, which drives the damper motor open. Once the damper
reaches the fully-open position, the end limit switch makes contact and closes the Air Damper Interlock
circuit, allowing the appliance to proceed to ignition. The diagram on the next page shows the wiring
necessary to install the normally-closed motorized damper.
Revised: January 3, 2020
Released: January 3, 2020
Maximum Allowable
Flue Vent Category
through Combustion
II
IV
3.4.5
Normally-Closed
Motorized Damper
10-0490-6946
10-0490-6989
 Patterson-Kelley 2020
All Rights Reserved.
P-K MACH
Technical Service 1.877.728.5351
Pressure Drop
Allowable Vent Pressure
Air Ductwork
0.22" W.C.
0.22" W.C.
for more information.
A
B
12"
12"
14"
14"
1004905981 P-K MACH C1500H-C4000 Installation and
Owners Manual (Rev F Jan-2020).docx
®
Gas Fired Boiler
-0.01" W.C. to
-0.04" W.C.
+0.01" W.C. to
+0.22" W.C.
C
D
15"
4.38"
17"
5.5"
Page 29