Propylene Glycol Flow
The table below summarizes the flow for the MACH appliances with different Propylene Glycol
mixtures:
Model 
Mixture 
Flow
0%
141.5 GPM
10%
143.2 GPM
20%
144.9 GPM
30%
147.5 GPM
40%
152.9 GPM
50%
159.9 GPM
60%
168.1 GPM
Model 
Mixture 
0%
10%
20%
30%
40%
50%
60%
Revised: January 3, 2020
Released: January 3, 2020
C1500H
Pressure Flow
13.2 ft
190.3 GPM
13.5 ft
192.6 GPM
13.8 ft
194.9 GPM
14.3 ft
198.3 GPM
15.4 ft
205.6 GPM
16.9 ft
215.0 GPM
18.6 ft
226.0 GPM
C3000
Flow
Pressure
273.4 GPM
21.8 ft
276.8 GPM
22.3 ft
280.0 GPM
22.8 ft
285.0 GPM
23.6 ft
295.4 GPM
25.4 ft
309.0 GPM
27.8 ft
324.7 GPM
30.7 ft
 Patterson-Kelley 2020
All Rights Reserved.
P-K MACH
Technical Service 1.877.728.5351
C2000H
Pressure Flow
15.7 ft
236.1 GPM
16.1 ft
239.0 GPM
16.5 ft
241.8 GPM
17.1 ft
246.1 GPM
18.4 ft
255.1 GPM
20.1 ft
266.8 GPM
22.2 ft
280.4 GPM
C4000
Flow
Pressure
376.6 GPM
15.4 ft
381.2 GPM
15.8 ft
385.7 GPM
16.2 ft
392.5 GPM
16.7 ft
406.9 GPM
18.0 ft
425.6 GPM
19.7 ft
447.2 GPM
21.7 ft
1004905981 P-K MACH C1500H-C4000 Installation and
Owners Manual (Rev F Jan-2020).docx
®
Gas Fired Boiler
C2500
Pressure
16.2 ft
16.6 ft
17.0 ft
17.6 ft
18.9 ft
20.7 ft
22.9 ft