Summary of Contents for EnerSys SuperSafe SBS XC

  • Page 1 Installation, Operation and Maintenance Manual Visit us at www.enersys.com...
  • Page 2 Batteries must be installed in accordance with the EN 50272-2 standard and any other local/national laws and regulations. 4. Installation Whatever your application, SuperSafe SBS XC batteries can be mounted in any orientation except inverted. However, in cyclic applications, EnerSys recommend to install 2 Volt DIN-size cells in horizontal orientation.
  • Page 3 The recommended float voltage temperature compensation is: • 2.29Vpc +3mV per cell per °C below 20°C Further details can be found in our SuperSafe SBS XC Operating Guide for Unreliable • 2.29Vpc -3mV per cell per °C above 20°C Grid Applications.