1
Check general wiring, as per heater manufacturer diagram.
Be sure you understand the system and its normal operation
2
Verify high voltage power supply wiring
Verify that correct voltage is present at the heater with proper wire size
Verify low voltage 24 Vac power supply wiring: 24 Vac is present at terminals 1 & 2 of the
3
R820 SCR
4
Create or simulate 100 % heating demand Using present control system
Signal between terminals 1 & 3 is 10 Vdc or superior
Dip switch properly configured: S1=Off, S2=Off, S3=Off & S4=On
Be sure that the polarity is correct and not reversed + to +, - to –
LED on SCR is on 100 % of the time
Signal between terminals 1 & 3 is 20 mA or superior
Dip switch properly configured: S1=Off, S2=Off, S3=On & S4=Off
Be sure that the polarity is correct and not reversed + to +, - to –
LED on SCR is on 100 % of the time
Verify amperage consumption of the heater: LED on SCR is on 100 % of the time
5
6
Verify & correct 24 Vac power supply to the SCR
Verify low voltage fuses, protections, flow switch,
7
Verify control wiring & control signal
Correct control signal is present at the SCR Check polarity of control signal
8
Verify fuses & all protections & contact the heater manufacturer
R820 Configured for 0 to 10 Vdc input signal
R820 Configured for 4 to 20 mA input signal