Facp Message Assignment - Speaker Specific; Facp Message Assignment - Zone Specific - Honeywell NOTIFIER NFC-50/100 Instruction Manual

Table of Contents

Advertisement

Programming
For non-General Alarm applications where input devices and/or messages are mapped to specific zones, Message 1 must be
removed from Zone 00 programming.

FACP Message Assignment - Speaker Specific

The NFC-50/100 has the capability of generating up to fourteen different messages. Any one of the fourteen messages can be pro-
grammed to each of the speaker circuit zones Z32 through Z56.
Example 1: If an addressable device programmed to Zone 35 is activated and no other devices are active, the message programmed for
Zone 35 will be generated over speaker circuit 3.
Addressable Pull Station
Example 2: If an addressable device (address 09 in example below) programmed to Zone 35 is activated and a second addressable
device (address 15 in example below) programmed to Zone 36 is activated, the highest priority message programmed to either Zone 35
or Zone 36 (Message 3 in example below) will be generated over speaker circuits 3 and 4. If an addressable device (address 21 in exam-
ple below) programmed to Zone 32 is then activated, the highest priority message programmed to Zone 32, 35, or 36 (Message 1 in
example below) will be generated over all speaker circuits.
Addressable Pull Station
(address 09)
Addressable Pull Station
(address 21)
Addressable Pull Station
(address 15)

FACP Message Assignment - Zone Specific

The FACP can be programmed to allow a specific addressable input device to generate one of fourteen messages over any speaker cir-
cuit. Any one of the fourteen messages can be programmed to each of the available zones (Zone 1 through Zone 99). In the following
example, assume that Zone 5 is programmed to Message 1, Zone 7 is programmed to Message 2, and Zone 35 is not programmed to a
message.
66
Programmed to
Zone 35
Message 3
Programmed to
Zone 35
Message 4
(lowest priority of the three)
Programmed to
Zone 32
Message 1
(highest priority of the three)
Programmed to
Zone 36
Message 3
(2nd highest priority of the three)
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018
Programmed Activation by FACP
Speaker Circuit 3
activate
Speaker Circuit 1
Speaker Circuit 2
Speaker Circuit 3
activate
Speaker Circuit 4
Speaker Circuit 5
Speaker Circuit 6
Speaker Circuit 7
Speaker Circuit 8
Speaker Circuit 9
Speaker Circuit 10
Speaker Circuit 11
Speaker Circuit 12
Speaker Circuit 13
Speaker Circuit 14
Speaker Circuit 15
Speaker Circuit 16
activate
Speaker Circuit 17
Speaker Circuit 18
Speaker Circuit 19
Speaker Circuit 20
Speaker Circuit 21
Speaker Circuit 22
Speaker Circuit 23
Speaker Circuit 24
activate