NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION AND OTHER INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units
and Accessories for Fire Alarm Systems, UL 864, and in the standard for Communication and Control Units for Mass Notification Systems, UL
2572, certain programming features or options must be limited to specific values or not used at all as indicated below:
Program feature or
option
UL 864/UL 2572? (Y/N)
AC Loss Delay
24 Hour Resound
Active With Page
Page Timeout
All NFC programming is done using the built-in web-based programming utility. It is recommended that tone selection, message repeat
cycles and background music options be reviewed and approved by the local AHJ.
To start programming, use a standard CAT5e Ethernet (patch) cable to connect a personal computer's IP port (Ethernet) to the IP port
(Ethernet) J2 on the main control board (right side of the board). Set the computer's local area network connection address as follows:
IP address: 169.254.3.5
Subnet mask: 255.255.0.0
NOTE: Be sure to record the computer's original addresses so they can be restored when NFC programming is complete.
Activate the PC's web browser (Google Chrome or Mozilla Firefox). Enter the following in the browser's navigation bar:
http://169.254.3.3
The main menu will display and allow further menu navigation.
NOTE: All screen shots reflect default programming.
Security and Data Protection:
NO ENCRYPTION EMPLOYED
Communication Security:
– a. Level 1
Stored Data Security:
– a. Level 0
Access Control Security:
– a. Level 1
Physical Security:
– a. Level 1
Audit Control: not provided

3.1 NFC-50/100 Panel Installation/Maintenance Security Checklist

System Description:_____________________________________________________
System Location: _______________________________________________________
Installer: _______________________________________ Date: __________________
Complete the following security tasks for each NFC-50/100 installation.

Install the NFC-50/100 panel in a secure location considering both software and hardware vulnerabilities.

Change the default password to a unique password.
Securely configure networks and firewalls.

Assess security risks.
Develop a Disaster and Recovery Plan.

Develop a Backup and Recovery Strategy.
Install, configure, and maintain anti-virus software on all computers which access the panel.

Keep the operating system updated and maintain version compatibility with the panel.
Deliver all required system information upon delivery to the system owner.

Train end-users on security maintenance tasks upon system delivery.
For decommissioning, dispose of data securely.

Ensure the Ethernet cable is removed from the NFC-50/100 when not being utilized for configuration.
Notifier FirstCommand Series Manual — P/N LS10001-001NF-E:H 1/8/2018

Section 3: Programming

Permitted in
Y
AC Loss Delay = 0, 2 (factory default), 6, 12, or 23 hours
Refer to "AC Loss Delay" on page 53.
Y
24 Hour Resound = Enabled
24 Hour Resound = Disabled
Refer to "24 Hour Resound" on page 53
N
Enable/Disable
N
0-60 in 15 second increments
Possible settings
Settings permitted in
UL 864/UL 2572
AC Loss Delay = 2 hours
24 Hour Resound Enabled
Disabled
0 seconds
51